Notes |
Date |
Text |
2003-10-06 00:00:00 | ***************** UNSAT **************** | | | | 1)NOTE: PLEASE SEE MISSING INFORMATION | | REQ'D ON TITLE BLOCK FOR ARCH'S. | | FAC AND FS 61G1-16.004/ 471. | | | | 2)NOTE: PLEASE SEE GEN LTS IS SHOWN W/ | | 60A OCP AND #6 AWG. PLEASE ADJUST. | | | | 3)NOTE: THIS IS ONLY A NOTE, PANEL IS | | STILL BEING SHOWN AS MCB, WHICH IS NOT | | REQ'D BUT PERMITTED. PLEASE JUST NOTE, | | IF SHOWN ON PLAN, THEN IT WILL BE REQ'D | | TO BE INSTALLED. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW, IF THERE ARE ANYU QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|