Plan Review Notes For Permit 03062012
Permit Number 03062012
Review Stop P
Sequence Number 2
Notes
Date Text
2003-08-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 AMENDMENTS. CHAPT. 1
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS NOR DOES IT REFLECT
 THE FLOOR PLAN.
 A) SANT. RISER SHOWS A SHOWER IN POWDER
 ROOM. FLOOR PLAN SHOWS NO SHOWER.
 B) TUB AND SHOWER IN MASTER BATH NOT
 VENTED PROPERLY. TABLE 906.1
 C) SEE RED LINE CORRECTION SHT A4 FOR
 CORRECT DIAGRAM FOR MASTER BATH. DELETE
 SHOWER AND RESUBMIT. SEC 104.2.1
  
 REVIEW BY KEN STEVENS