Plan Review Notes For Permit 03062012 |
Permit Number |
03062012 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-08-15 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 AMENDMENTS. CHAPT. 1 | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | CODE REQUIREMENTS NOR DOES IT REFLECT | | THE FLOOR PLAN. | | A) SANT. RISER SHOWS A SHOWER IN POWDER | | ROOM. FLOOR PLAN SHOWS NO SHOWER. | | B) TUB AND SHOWER IN MASTER BATH NOT | | VENTED PROPERLY. TABLE 906.1 | | C) SEE RED LINE CORRECTION SHT A4 FOR | | CORRECT DIAGRAM FOR MASTER BATH. DELETE | | SHOWER AND RESUBMIT. SEC 104.2.1 | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|