Plan Review Notes For Permit 03062000 |
Permit Number |
03062000 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-07-03 00:00:00 | DENIED | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | A) PLEASE ADJUST YOUR NOTES, DETAILS, OR | | SUBMITTALS TO REFLECT THE FOLLOWING IN- | | FORMATION REQUIRED FOR PLAN REVIEW | | 1) FBC-2001424.2.6.6.2 SHOW COMPLIANCE | | WITH ANSI/ASME A112.19.8M. PROVIDE MODEL | | NUMBER AND MANUF INFO FOR VAC LOCK. | | (GIVE DETAIL OR ADD NOTE)(SUBMITTAL) | | 2) FBC-2001424.2.6.6.5 WHERE PROVIDED, | | THE VACUUM OR PRESSURE CLEANER FITTING | | SHALL BE LOCATED AT LEAST 6" AND NOT | | GREATER THAN 12" BELOW THE MINIMUM OPER- | | ATING WATER LEVEL OR AS AN ATTACHMENT TO | | THE SKIMMER. | | 3) FBC-2001 424.2.14.2 WATER RETENTION, | | PROVIDE A POSITIVE MEANS OF RETAINING | | WATER IN THE HEATER WHEN PUMP IS SHUT | | OFF. (MANUFACTURE CUT SHEETS SUBMITTAL) | | 4) FBC-2001 424.2.14.4 CONNECTIONS, ALL | | WATER HEATING EQUIPMENT SHALL BE INSTAL- | | LED WITH FLANGES OR UNION CONNECTIONS | | ADJACENT TO THE HEATER. (ADD TO NOTES) | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 |
|