Plan Review Notes
Plan Review Notes For Permit 03061862
Permit Number 03061862
Review Stop E
Sequence Number 3
Notes
Date Text
2004-05-28 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3. 20 AMP.
  
 2} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 3} THE SMALL APPLIANCE CIRCUITS MUST BE
 20 AMP #12 WIRE PER 210.52(B)(1), ALSO
 THE DINING ROOM, SAME ARTICLE.
  
 4} THERE MUST BE A RECEPTACLE ADDED TO
 THE KITCHEN COUNTERTOP TO COMPLY WITH
 210.52(C)(1).
  
 5} THE SMOKE DETECTOR IN THE UPSTAIR
 HALL MUST BE 3'FROM THE BATH DOOR. SEE
 8-1.4.2 NFPA-72.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW