Plan Review Notes For Permit 03061862 |
Permit Number |
03061862 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2004-05-28 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE LIST ALL THE REQUIRED | | DEDICATED BATH(S) CIRCUIT(S) ON PANEL | | SCHEDULE. PER 210.52D, 210.11C3. 20 AMP. | | | | 2} PLEASE LIST THE REQUIRED ARC | | FAULT PROTECTED CIRCUIT(S) ON PANEL | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | IN BEDROOMS ARE TO BE PROTECTED , | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | | 3} THE SMALL APPLIANCE CIRCUITS MUST BE | | 20 AMP #12 WIRE PER 210.52(B)(1), ALSO | | THE DINING ROOM, SAME ARTICLE. | | | | 4} THERE MUST BE A RECEPTACLE ADDED TO | | THE KITCHEN COUNTERTOP TO COMPLY WITH | | 210.52(C)(1). | | | | 5} THE SMOKE DETECTOR IN THE UPSTAIR | | HALL MUST BE 3'FROM THE BATH DOOR. SEE | | 8-1.4.2 NFPA-72. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|