2004-06-07 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 03061862 |
| ADD: 819 HANSEN ST |
| CONT:SJE DESIGN & CONSTRUCTION |
| TEL: (561)478-5670 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 3RD REVIEW |
| ACTION: DENIED, EXPIRED, NO WORK WITHIN |
| 6 MONTHS |
| |
| NOTE: THE ELECTRIC / BUILDING REVIEWS |
| HAVE BEEN COMPLETED BUT A NEW PERMIT |
| WILL HAVE TO BE APPLIED FOR, WPB |
| ADMINISTRATIVE CODE 104.1.6 TIME LIMIT- |
| ATIONS. |
| |
| 1) PLANS ARE TO INDIATE WHAT CRITERIA |
| THE BUILDING IS TO BE BUILT: |
| FL. BLD CODE 1606.1.7 THE FOLLOWING |
| INFORMATION RELATED TO WIND SHALL BE |
| SHOWN ON THE CONSTRUCTION DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| |
| THE TRUSS DESIGN CRITERIA HAS THIS INFOR |
| MATION, BUT NO WHERE DOES THE STRUCTURE |
| INDICATE THE SAME CRITERIA WAS USED. |
| |
| IN THE TRUSS DESIGN CRITERIA NO BOTTOM |
| CHORD LIVE LOAD IS GIVEN, TABLE 1604.1 |
| ATTICS WITHOUT STORAGE REQUIRE 10 LBS. |
| |
| 2)FBC 13-103.1.2 BEFORE A BUILDING |
| PERMIT CAN BE ISSUED, THE SUBMITTED |
| ENERGY CODE COMPLIANCE FORMS SHALL BE |
| SIGNED BY THE BUILDING OWNER, THE |
| OWNER'S ARCHETECT OR OTHER AUTHORIZED |
| AGENT LEGALLY DESIGNATED BY THE OWNER. |
| |
| 3) PRODUCT APPROVALS: SINCE THE NEWLY |
| APPLIED FOR PERMIT WILL HAVE A DATE |
| AFTER OCT.1 2003 THE STATEWIDE PRODUCT |
| APPROVAL SYSTEM IS IN AFFECT. |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 4) SOME PRODUCT APPROVALS SUBMITTED ARE |
| DUPLICATE FOR THE SAME USE, ROOFING |
| PULL THE REPORT NOT TO BE USED. |
| |
| 5) UNDER THE NEW STATEWIDWE PRODUCT |
| APPROVAL SYSTEM THE TRUSS ANCHORS ARE |
| ALSO REQUIRED TO HAVE THE STATE LISTING. |
| ONCE YOU HAVE THE PRODUCT APPROVALS AND |
| STATE LISTING HIGHLIGHT EACH ANCHOR TO |
| BE USED. |
| |
| 6) THERE HAS BEEN NO PRODUCT TESTING |
| REPORT FOR THE GARAGE DOOR. |
| |
| 7) STORM SHUTTERS PROVIDE THE FOLLOWING: |
| FL BLD CODE 2001 SECTION 103.6, |
| 1606.1.4, 1707.4 & 3401.7.2.4. |
| PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| SCHEDULE SUMMARIZING & IDENTIFYING |
| OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| BAR REINFORCING REQUIREMENTS, WALL PRES- |
| SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| SUBMITTED AT TIME OF PERMIT APPLICATION |
| TO FACILITATE PLAN REVIEW AND PERMIT |
| ISSUANCE.SEE SAMPLE ATTACHED. |
| |
| 8)1707.4.5.1 MULLIONS OCCURRING |
| BETWEEN INDIVIDUAL WINDOW AND GLASS |
| DOOR ASSEMBLIES. TESTING REPORTS ARE |
| REQUIRED BY AN APPROVED TESTING |
| LABORATORY OR BE ENGINEERED.ALSO WILL RE |
| QUIRE STATE APPROVAL. |
| |
| 9)2305.2.2 FLOOR/CEILING ASSEMBLIES |
| SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL/ |
| ING ASSEMBLIES SEPERATING USEABLE SPACE |
| INTO 2 OR MORE APPROXIMATE AREAS WITH NO |
| AREA GREATER THAN 500 SQ FT. DRAFTSTOP- |
| PING SHALL BE PROVIDED PARALLEL TO THE |
| MAIN FRAMING MEMBERS. |
| |
| 10)PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |