2004-06-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03061862
 ADD: 819 HANSEN ST
 CONT:SJE DESIGN & CONSTRUCTION
 TEL: (561)478-5670
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 3RD REVIEW
 ACTION: DENIED, EXPIRED, NO WORK WITHIN
 6 MONTHS
  
 NOTE: THE ELECTRIC / BUILDING REVIEWS
 HAVE BEEN COMPLETED BUT A NEW PERMIT
 WILL HAVE TO BE APPLIED FOR, WPB
 ADMINISTRATIVE CODE 104.1.6 TIME LIMIT-
 ATIONS.
  
 1) PLANS ARE TO INDIATE WHAT CRITERIA
 THE BUILDING IS TO BE BUILT:
 FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 THE TRUSS DESIGN CRITERIA HAS THIS INFOR
 MATION, BUT NO WHERE DOES THE STRUCTURE
 INDICATE THE SAME CRITERIA WAS USED.
  
 IN THE TRUSS DESIGN CRITERIA NO BOTTOM
 CHORD LIVE LOAD IS GIVEN, TABLE 1604.1
 ATTICS WITHOUT STORAGE REQUIRE 10 LBS.
  
 2)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 3) PRODUCT APPROVALS: SINCE THE NEWLY
 APPLIED FOR PERMIT WILL HAVE A DATE
 AFTER OCT.1 2003 THE STATEWIDE PRODUCT
 APPROVAL SYSTEM IS IN AFFECT.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4) SOME PRODUCT APPROVALS SUBMITTED ARE
 DUPLICATE FOR THE SAME USE, ROOFING
 PULL THE REPORT NOT TO BE USED.
  
 5) UNDER THE NEW STATEWIDWE PRODUCT
 APPROVAL SYSTEM THE TRUSS ANCHORS ARE
 ALSO REQUIRED TO HAVE THE STATE LISTING.
 ONCE YOU HAVE THE PRODUCT APPROVALS AND
 STATE LISTING HIGHLIGHT EACH ANCHOR TO
 BE USED.
  
 6) THERE HAS BEEN NO PRODUCT TESTING
 REPORT FOR THE GARAGE DOOR.
  
 7) STORM SHUTTERS PROVIDE THE FOLLOWING:
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.SEE SAMPLE ATTACHED.
  
 8)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.ALSO WILL RE
 QUIRE STATE APPROVAL.
  
 9)2305.2.2 FLOOR/CEILING ASSEMBLIES
 SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL/
 ING ASSEMBLIES SEPERATING USEABLE SPACE
 INTO 2 OR MORE APPROXIMATE AREAS WITH NO
 AREA GREATER THAN 500 SQ FT. DRAFTSTOP-
 PING SHALL BE PROVIDED PARALLEL TO THE
 MAIN FRAMING MEMBERS.
  
 10)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715