Date Text
2003-08-26 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} ENGINEERS # MISSING FROM TITLE BLOCK.
 SEE FAC 61G15-23.002(2).
  
 2} CHANGES TO ENGINEERED PLANS MUST BE
 MADE BY THE ENGINEER OF RECORD,AND
 INITIALED BY SAME.THE CHANGES TO THIS
 PLAN AND CALCULATIONS RENDER PARTS OF
 IT ILLEGIBLE.PLEASE REDRAW THE PLANS
 LEAVING ONLY PERTINENT INFORMATION PER
 104.2.1 FBC & LOCAL AMMENDMENTS.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 4} PLEASE NOTE PER 250.50 ALL ITEMS
 AVAILABLE MUST BE USED TO FORM THE GEC
 SYSTEM.IG: FOOTER STEEL & CWP.
  
 5} PLEASE RECALCULATE THE LOAD PER
 ARTICLE 220.THE SERVICE APPEARS TO BE
 TOO SMALL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW