2003-09-15 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 03061862 |
| ADD: 819 HANSEN STREET |
| CONT:SUINGLIO ESPEJO |
| TEL: (561)305-0244 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 2ND REVIEW |
| |
| 1) THE FOURTH QUESTION FROM THE FIRST RE |
| VIEW, SHEET A-1 SHOWS THAT THE CATEGORY |
| ISTHEN THERE IS A "B" AND "C", EITHER |
| CIRCLE OR "X" OUT THE ONE NOT USED. |
| DO THE SAME FOR "SATUS"!!!!!!!!!!!!! |
| |
| 2) SHEET A-2 NOT THE BOTTOM OF THE |
| FOUNDATION TO BE 8" BELOW GRADE.WRONG! |
| 1804.1.3 THE BOTTOM OF THE FOUNDA- |
| TION SHALL EXTEND NO LESS THAN 12" |
| BELOW FINISH GRADE. |
| |
| 3) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORT, SBCCI OR DADE COUNTY |
| REPORT ARE ACCEPTED. MISSING REPORTS: |
| A) SLIDING GLASS DOOR |
| B) PAIR OF FRENCH DOORS W/ SIDELITES |
| |
| 4) MISSING BEAM INFORMATION, NO LAYOUT |
| OF BARS REQUIRED OR SIZE, STIRRUPS ETC? |
| SAME COMMENT AS 1ST REVIEW! |
| |
| 5) SECOND FLOOR ALSO MISSING INFORMATION |
| AS TO WHAT MATERIAL IT IS MADE FROM? |
| NO 2ND STORY FRAMING PLAN, THE SECTION |
| PROVIDED FOR FIRST FLOOR REFER TO BOND |
| BEAM SCHEDULE? WHERE? |
| STRAPING NOTE SEE DETAIL 1/S2? WHERE? |
| SAME COMMENTS FROM 1ST REVIEW!!! |
| UPLIFT STRAPS FEFER TO ROOF FRAMING |
| PLAN? WHERE? |
| ROOF NAILING NOT TO CITY W. P. B. |
| TABLE 2306.1 6" EDGE/ 6" INTERMEDIATES! |
| |
| 6) 1707.3.1 JOIST HANGERS, FRAMING |
| ANCHORS & SIMILAR DEVICES SHALL BE TEST- |
| ED IN ACCORDANCE W/ ASTM D 1761 & BE |
| LABELED AND LISTED FOR THEIR LOAD CARRY- |
| ING CAPACITY. |
| INDICATE ON THE ROOF FRAMING PLAN THIS |
| INFORMATION. |
| 1609.4.3 LOAD REDUCTION. |
| WHEN STRUCTURAL EFFECTS DUE TO TWO OR |
| MORE LOADS IN COMBINATION WITH DEAD LOAD |
| ARE INVESTIGATED IN LOAD COMBINATIONS OF |
| 1609.4.1 OR 1609.4.2, THE COMBINED |
| EFFECTS DUE TO THE TWO OR LOADS MULTI- |
| PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD |
| LOADS SHALL NOT BE LESS THAN THE EFFECTS |
| FROM THE LOAD COMBINATION OF THE DEAD |
| LOAD PLUS THE LOAD PRODUCING THE LARGEST |
| EFFECTS. INCREAS IN ALLOWABLE STRESS SPE |
| CIFIED IN THE MATERIALS SECTIONS OF THIS |
| CODE OR A REFRENCED STANDARD SHALL NOT |
| BE USED WITH THESE LOAD COMBINATIONS |
| EXCEPT THAT A DURATION OF LOAD INCREASE |
| SHALL BE PERMITTED IN ACCORDANCE WITH |
| CHAPTER 23. |
| |
| 7) 1707.4.4.2 TAPERED BUCKS: |
| SHALL EXTEND BEYOND THE INTERIOR FACE |
| OF THE WINDOW OR DOOR FRAME SUCH THAT |
| FULL SUPPORT OF THE FRAME IS SUPPORTED. |
| |
| 8) PROVIDE (2) COPIES OF ENERGY SHEETS, |
| ALL PRODUCT APPROVALS TO BE SUBMITTED. |
| |
| 9)BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| PLANS REQUIRE COUNTY STAMP REVIEWED!!!!! |
| |
| 10)PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |