Notes |
Date |
Text |
2003-07-15 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | NOTE: PLEASE NOTE THAT ALL PLANS | | THAT ARE SIGNED AND SEALED BY ARCH/ OR | | ENGINEER ARE REQ`D PER 61G15-23.002 FOR | | ENGINEER AND 61G1-16.004 FOR ARCH. | | SHALL HAVE A TITLE BLOCK.ALSO PLEASE | | INITIAL ALL CHANGES. | | | | PLEASE NOTE THAT THE GROUNDING ELECTRODE | | SYSTEM MUST USE ALL ITEMS AVAILABLE PER | | 250-50(A)-(D). | | | | PLEASE SHOW ALL WIRE AND BREAKER SIZES | | ON THE PANEL SCHEDULE. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|