Plan Review Notes
Plan Review Notes For Permit 03061862
Permit Number 03061862
Review Stop E
Sequence Number 1
Notes
Date Text
2003-07-15 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 NOTE: PLEASE NOTE THAT ALL PLANS
 THAT ARE SIGNED AND SEALED BY ARCH/ OR
 ENGINEER ARE REQ`D PER 61G15-23.002 FOR
 ENGINEER AND 61G1-16.004 FOR ARCH.
 SHALL HAVE A TITLE BLOCK.ALSO PLEASE
 INITIAL ALL CHANGES.
  
 PLEASE NOTE THAT THE GROUNDING ELECTRODE
 SYSTEM MUST USE ALL ITEMS AVAILABLE PER
 250-50(A)-(D).
  
 PLEASE SHOW ALL WIRE AND BREAKER SIZES
 ON THE PANEL SCHEDULE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718