2003-07-17 00:00:00 | ******CORRECTIONS****** |
| |
| SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)THE PLANS SHOW A FIREPLACE. INCLUDE |
| THIS IN THE PROJECT DESCRIPTION OF YOUR |
| PERMIT APPLICATION. |
| |
| 2.)ENGINEER TITLE BLOCK REQUIRED, |
| FAC61G15-23.002. |
| |
| 3.)THE SQUARE FOOTAGE OF LIVING SPACE |
| IS BEING INCREASED (BETWEEN LIVING ROOM |
| TO NEW CARPORT, FIREPLACE).THIS IS |
| NOT REFLECTED ON THE IMPACT FEE STAMP. |
| |
| 4.)PROVIDE AREA CALCULATIONS - |
| EXISTING CONDITIONED AND UNCONDITIONED |
| SPACE, PROPOSED, SUBTOTALS, NEW TOTAL. |
| |
| 5.)ENERGY CALCS REQUIRED FBC13-101.2. |
| |
| 6.)SOFFIT VENTS CANNOT "MATCH |
| EXISTING", THEY MUST COMPLY WITH |
| FBC2309.7. |
| |
| 7.)ON THE WALL SECTION, SHOW THE |
| MINIMUM DIMENSIONS ABOVE AND BELOW |
| GRADE FOR THE FOUNDATION, FBC1804.1.3, |
| CITY OF WPB AMENDMENTS TO THE FBC |
| 1804.1.7. |
| |
| 8.)PROVIDE A ROOF SHEATHING NAILING |
| SCHEDULE, CITY OF WPB AMENDMENTS TO |
| THE FBC TABLE 2306.1. |
| |
| 9.)IS THE PROPOSED DRIVEWAY SHOWN ON |
| THE SITE PLAN TO BE ON THIS PERMIT? IF |
| IT IS, ADD IT TO YOUR APPLICATION.THE |
| SITE PLAN AND SURVEY CONFLICT AS TO |
| THE DRIVEWAY CONFIGURATION. |
| |
| 10.) THE SITE PLAN SUBMITTED FOR |
| ZONING SHOWS ONLY A CARPORT.THE SITE |
| PLAN SHOULD SHOW ALL IMPROVEMENTS - |
| CARPORT, PORCH, LIVING AREA.REVISE. |
| |
| 11.)SUBMIT TWO COPIES OF THE |
| FOLLOWING PRODUCT APPROVALS: |
| SHINGLES |
| DOORS |
| TRANSOM WINDOWS |
| IMPACT PROTECTION FOR GLAZING |
| |
| 12.)SHOW THE MINIMUM DIMENSIONS ABOVE |
| THE ROOF FOR THE CHIMNEY, FBC2804.2.4. |
| |
| 13.)PROVIDE INFORMATION FOR THE |
| FACTORY BUILT FIREPLACE AND CHIMNEY. |