Plan Review Notes
Plan Review Notes For Permit 03061497
Permit Number 03061497
Review Stop E
Sequence Number 1
Notes
Date Text
2003-07-08 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE CLARIFY IF AHU/WH IN
 STORAGE IS NEW OR BEING RELOCATED?
 IF NEW, PROVIDE INFORMATION AND LOAD
 CALCULATIONS.
  
 2)NOTE: PLANS ARE NOTED TO SEE E-SHEETS
 FOR ELECTRICAL LAYOUT? NO E-SHEETS WERE
 SUBMITTED FOR REVIEW.
  
 3)NOTE: PLANS ARE ALSO SHOWING NEW FOYER
 /VERANDA'S AND CANTINA WITH NOTHING
 SUBMITTED FOR REVIEW?
 EGRESS LIGHTING? GFI RECEPTS? ETC
 210-8/210-70
  
 PLEASE NOTE, THERE MAY BE FURTHER
 COMMENTS, DUE TO THE PLANS NOT BEING
 COMPLETE AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]