2003-07-14 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 03061290 |
| ADD: 2491 OKEECHOBEE BLVD SIUTE "E" |
| CONT: LEIGHTEN MCGINN |
| TEL: (561)722-9696 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1)FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| INFORMATION ON THE SECURITY GRILL, MAN- |
| UFCTURERS SPEC. LBS/ FT |
| |
| 2)FIGURE 1606 WIND-BORNE DEBRIS |
| REGION; INDICATES THAT W.P.B. CITY OF IS |
| LOCATED IN THE 140 MPH ZONE. PLANS ARE |
| TO INDICATE THIS. |
| |
| 3)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| INFORMATION RELATED TO WIND SHALL BE |
| SHOWN ON THE CONSTRUCTION DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| |
| PLANS INDICATE (1) NEW DOOR IN THE FRONT |
| AND (1) NEW DOOR TO THE REAR. |
| |
| 4) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORT, SBCCI OR DADE COUNTY |
| REPORT ARE ACCEPTED. MISSING REPORTS: |
| A) NEW FRONT DOOR GLAZED |
| B) NEW REAR DOOR |
| |
| 5) 1707.4.3 EACH EXTERIOR DOOR |
| ASSEMBLY NOT COVERED BY 1707.4.2 |
| (GLAZED DOORS) SHALL BE LISTED AND TEST- |
| ED FOR A PERIOD EQUAL TO THE QUANITY |
| 3600/ V WHERE THE TIME PERIOD IS IN |
| SECTIONS AND V IS IN MILES PER HR TAKEN |
| FROM FIGURE 1606. THE TIME PERIOD SHALL |
| ALSO INCLUDE A 10 SECOND PERIOD AT A |
| LOAD EQUAL TO 1.5 TIMES THE DESIGN |
| PRESSURE. DADE COUNTY & SBCCI REPORTS |
| ARE ACCEPTED. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| JIM WITMER |
| BUILDING PLAN REVIEW |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |