Plan Review Notes
Plan Review Notes For Permit 03060960
Permit Number 03060960
Review Stop E
Sequence Number 2
Notes
Date Text
2003-08-05 00:00:00************* PROVISO/REVISION *******
  
 PLEASE SEE NOTES FROM FIRST AND SECOND
 REVIEW.
  
 1)NOTE: PLEASE SUBMIT COMPLETE CIRCUIT-
 -ING AND CORRELATE WITH SUBMITTED PANEL
 SCHEDULES. PLEASE SEE TWO DIFFERENT
 SETS OF PANELS ARE SHOWN.
  
 2)NOTE: PLEASE SEE MISSING REQ'D SIGN
 CIRCUIT PER 600-5.
  
 3)NOTE: PLEASE SEE 700-12E FOR CIRCUIT-
 -ING OF EM/ EXT LTS.
  
 4)NOTE; PLEASE SEE THAT CIRCUITS SHOWN
 ON PLANS DO NOT CORRELATE W/ PANELS,
 EXAMPLE, A-6 FOR GEN RECEPTS ARE SHOWN
 AS A WATER HEATER CIRCUIT??
  
  
 PLEASE REVISE AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW BEFORE ANY ROUGH
 ELECTRICAL INDSPECTION IS CALLED IN.
 IF THERE ARE NAY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 PLEASE SEE THAT THREE NEW PANEL SCHEDULE
 -S SHOWN ON PLANS HAVE BEEN STRIKED
 THROUGH. PLEASE SEE THAT THESE DO NOT
 MATCH AND NUMEROUS ITEMS ON SCHEDULES
 DO NOT HAVE CORRECT OCP/AWG/ FOR LOADS
 ETC.
 PLEASE SEE PROVISO SET FORTH.