Notes |
Date |
Text |
2003-08-05 00:00:00 | ************* PROVISO/REVISION ******* | | | | PLEASE SEE NOTES FROM FIRST AND SECOND | | REVIEW. | | | | 1)NOTE: PLEASE SUBMIT COMPLETE CIRCUIT- | | -ING AND CORRELATE WITH SUBMITTED PANEL | | SCHEDULES. PLEASE SEE TWO DIFFERENT | | SETS OF PANELS ARE SHOWN. | | | | 2)NOTE: PLEASE SEE MISSING REQ'D SIGN | | CIRCUIT PER 600-5. | | | | 3)NOTE: PLEASE SEE 700-12E FOR CIRCUIT- | | -ING OF EM/ EXT LTS. | | | | 4)NOTE; PLEASE SEE THAT CIRCUITS SHOWN | | ON PLANS DO NOT CORRELATE W/ PANELS, | | EXAMPLE, A-6 FOR GEN RECEPTS ARE SHOWN | | AS A WATER HEATER CIRCUIT?? | | | | | | PLEASE REVISE AND SUBMIT THE ABOVE | | INFORMATION FOR REVIEW BEFORE ANY ROUGH | | ELECTRICAL INDSPECTION IS CALLED IN. | | IF THERE ARE NAY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | | PLEASE SEE THAT THREE NEW PANEL SCHEDULE | | -S SHOWN ON PLANS HAVE BEEN STRIKED | | THROUGH. PLEASE SEE THAT THESE DO NOT | | MATCH AND NUMEROUS ITEMS ON SCHEDULES | | DO NOT HAVE CORRECT OCP/AWG/ FOR LOADS | | ETC. | | PLEASE SEE PROVISO SET FORTH. |
|