Plan Review Notes For Permit 03060835 |
Permit Number |
03060835 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2003-10-06 00:00:00 | ************ UNSAT *************** | | | | 1)NOTE: PLEASE SEE LICENSE INFORMATION | | REQ'D ON TITLE BLOCK. 61G1-16.004 | | | | 2)NOTE: PLEASE SEE GEN LT SHOWN WITH | | 60A OCP AND #6 AWG. PLEASE ADJUST. | | | | 3)NOTE: PLEASE SEE MISSING SDIN THE | | IMMEDIATE VICINITY OF STAIRS LEADING TO | | FLOOR ABOVE. NFPA-72 | | | | 4)NOTE: PLEASE NOTE, PANEL IS STILL | | SHOWN AS A MCB PANEL.THIS IS PERMITTED | | BY CODE, HOWEVER NOT REQ'D. THIS IS ONLY | | A NOTE; IF SHOWN ON PLAN, THEN IT WILL | | BE REQ'D TO BE INSTALLED. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|