Plan Review Notes
Plan Review Notes For Permit 03060835
Permit Number 03060835
Review Stop E
Sequence Number 3
Notes
Date Text
2003-10-06 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE LICENSE INFORMATION
 REQ'D ON TITLE BLOCK. 61G1-16.004
  
 2)NOTE: PLEASE SEE GEN LT SHOWN WITH
 60A OCP AND #6 AWG. PLEASE ADJUST.
  
 3)NOTE: PLEASE SEE MISSING SDIN THE
 IMMEDIATE VICINITY OF STAIRS LEADING TO
 FLOOR ABOVE. NFPA-72
  
 4)NOTE: PLEASE NOTE, PANEL IS STILL
 SHOWN AS A MCB PANEL.THIS IS PERMITTED
 BY CODE, HOWEVER NOT REQ'D. THIS IS ONLY
 A NOTE; IF SHOWN ON PLAN, THEN IT WILL
 BE REQ'D TO BE INSTALLED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]