Plan Review Notes
Plan Review Notes For Permit 03060831
Permit Number 03060831
Review Stop E
Sequence Number 2
Notes
Date Text
2004-08-03 00:00:00******** UNSAT ************
  
 1)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 PLEASE SEE MISSING SD ON LOWER LEVEL
 LEADING TO FLR ABOVE. PLEASE ALSO SEE
 SD TO BE MOVED INTO MASTER BEDRM.
  
 2)NOTE: PLEASE SEE MISSING LICENSE #'S
 ON TITLE BLOCKS PER FS 481.219 AND
 FAC 61G1-16.004.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]