Plan Review Notes For Permit 03060735 |
Permit Number |
03060735 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-07-01 00:00:00 | DENIED:MECHANICAL PERMIT 03060742 | | | | ENERGY CALCULATIONS - 1 SET INIDCATES | | 58,500 BTU'S FOR 2567 SQ FT & MANUAL J | | CALCS INDICATE 38,646 BTU'S.THE OTHER | | SET OF ENERGY CALCS INDICATE 47,000 | | BTU'S FOR 2300 SQ FT. EQUIPMENT SCHEDULE | | INDICATES 58,500 BTU'S & 2567 SQ FT. | | | | PLEASE CORRECT & RESUBMIT. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|