Plan Review Notes For Permit 03060706 |
Permit Number |
03060706 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-07-21 00:00:00 | BUILDING PROVISO | | | | 1) STRUCTURE IS LOCATED IN AN AO FLOOD | | ZONE AN ELEVATION WILL BE REQUIRED. | | | | 2) SUBMIT A CORRECTED INSTALLATION | | SCHEDULE AND A KEY PLAN FOR THE STORM | | PANELS PRIOR TO INSTALLATION. | | | | 3) SUBMIT REVISED WINDLOADS FOR ALL | | EXTERIOR OPENINGS BASED ON EXPOSURE | | CATEGORY B. | | | | 4) SUBMIT A REVISED CONNECTOR SCHEDULE | | FOR THE TRUSSES WHICH DOES NOT INCLUDE | | A 1/3 INCREASE ON THE STEEL CALCULATIONS | | PRIOR TO INSTALLATION OF TRUSSES. | | | | 5) SUBMIT CURRENT PRODUCT APPROVALS FOR | | THE HORIZONTAL SLIDING WINDOWS, PRIOR TO | | INSTALLATION. |
|