Plan Review Notes For Permit 03060694 |
Permit Number |
03060694 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-07-14 00:00:00 | | | *** ISSUED PERMIT*** | | -PLAN REVIEW HISTORY- | | | | PERMIT# 03060694 | | ADDRESS: 23250 MORGANS BLUFF | | CONT: SIERRA | | TELL # (561) 616-9686 | | | | THE ATTACHED COMMENTS ARE PART OF THE | | PERMIT AND PLAN REVIEW PACKAGE AND ARE | | NOT TO BE REMOVED FROM THE ISSUED SET OF | | PLANS.104.2.1.2 ADMINISTRATIVE CODE. | | | | ******BUILDING PROVISO******** | | | | 1) DISCREPANCY BETWEEN THE ENERGY CALS& | | THE FLOOR PLAN ( SQ FT). | | | | 2) STORM SHUTTERS: | | A) PROVIDE A KEY PLAN. | | B) BOTTOM FASTENER CAULK-IN, THE VALUE | | TAKEN IS FOR CONCRETE, NOT CEMENT BLOCK! | | THIS FASTENER MAY NOT BE USED IN BLOCK, | | OR IF THIS IS USED IN FILLED CELL, THE | | CAULK-IN MUST BE IN 2500 PSI CONCRETE | | (FILLED CELL). OTHER ALTERNATIVE IS A | | DIFFERENT FASTENER FOR BLOCK. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|