Plan Review Notes For Permit 03060668 |
Permit Number |
03060668 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-06-20 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE CORRECT THE FOLLOWING FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} ADD RECEPTACLE IN THE GREAT ROOM TO | | COMPLY WITH 210-52(A)(2)(A). | | | | 2} PLEASE LIST THE REQ'D BATH(S) | | CIRCUIT(S). PER 210-11-C-3 | | MUST BE 20A AND #12AWG. | | | | 3} PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 4} PLEASE NOTE THAT ALL PLANS | | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- | | ING A TITLE BLOCK, MUST BE SIGNED, DATED | | AND SEALED BY THE ARCH/ENGINEER OF | | RECORD. PER FS/FAC 481.221 & 471.025 | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|