Plan Review Notes
Plan Review Notes For Permit 03060668
Permit Number 03060668
Review Stop B
Sequence Number 1
Notes
Date Text
2003-07-17 00:00:00DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT A SOIL BORING TEST REPORT AS
 REQUIRED BY CITY AMENDMENTS TO FBC
 1804.2.2.
  
 4) THE CONTRACTOR'S SIGNATURE ON THE
 PERMIT APPLICATION IS NOT NOTARIZED.
  
 5) SAFETY GLAZING IS REQUIRED IN THE
 BATHROOM WINDOWS PER FBC 2405.2.1.
  
 6) THE 34 ROLLING WINDOW IN THE MASTER
 BEDROOM MUST COMPLY WITH FBC 1005.4.4
 FOR EMERGENCY ESCAPE AND RESCUE. SUBMIT
 THE CLEAR OPENING DIMENSIONS FOR THIS
 WINDOW.
  
 7) PROVIDE PRODUCT APPROVALS FOR THE
 HORIZONTAL SLIDING WINDOW.
  
 8) THE WIRE MESH IN THE SLAB IS REQUIRED
 TO BE SUPPORTED PER FBC 1909.3.
  
 9) REVISE NOTE #11 ON SHEET 3. INTERIOR
 DRYWALL FASTENER SPACING FOR 1-3/8" AND
 1-1/2" DRYWALL NAILS IS 7" O.C. ON
 CEILINGS AND 8" O.C. ON WALLS PER FBC
 TABLE 2306.1.
  
 10) INDICATE ON PLANS THAT THE FINISH
 FLOOR ELEVATION AT HABITABLE AREAS IS A
 MINIMUM OF 4" ABOVE FINISH GRADE PER
 CITY AMENDMENTS TO FBC 1804.1.7.
  
 12) SPECIFY ON PLAN THAT THE BOTTOM OF
 FOOTINGS IS REQUIRED TO BE A MINIMUM OF
 12" BELOW FINAL GRADE PER FBC 1804.1.
  
 13) PROVIDE A BUCK DETAIL FOR THE SIDE
 SWING EXTERIOR FRONT DOOR.
  
 14) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. INDICATE
 THE CONNECTION TYPE AND ANCHOR TYPES ON
 THE PRODUCT APPROVAL THAT WILL BE USED.
  
 15) THE OWNER/AGENT IS REQUIRED TO SIGN
 AND DATE THE ENERGY CALCULATION FORM
 600A.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714