2003-06-20 00:00:00 | *********** UNSAT *************** |
| |
| 1)NOTE: PLEASE SEE NOTES TO ELEC. |
| WORK PER PALM BEACH COUNTY. PLEASE NOTE, |
| CITY OF WEST PALM BEACH. |
| |
| 2)NOTE: PLEASE SEE 210-52D/210-11C3, |
| DEDICATED BATH(S) CIRCUITS REQ`D TO BE |
| #12 AWG, AND 20A. |
| |
| 3)NOTE: PLEASE CLARIFY WASHER/LAUNDRY, |
| WASHER SHOWN AT 1.2KW(1.5REQ`D) BUT |
| LAUNDRY RECEPT SHOWN AT 1.5KW? |
| WHICH ONE? |
| |
| 4)NOTE: PLEASE SUBMIT AIC RATING FOR |
| NEW SERVICE EQUIPMENT. 110-9,215-5 |
| MAINS/PANELS/BRKRS ARE ALL TO RATED FOR |
| THE AVAILABLE FAULT CURRENT. |
| |
| 5)NOTE:PLEASE SEE FS/FAC PLANS CONTAIN- |
| -ING A TITLE BLOCK, MUST BE SIGNED, |
| DATED AND SEALED BY THE ARCH/ENGINEER OF |
| RECORD. 471.025/184.221 |
| |
| 6)NOTE: PLEASE SEE 250-110,250-122, FOR |
| EQUIPMENT GROUNDING CONDUCTOR BETWEEN |
| MAIN AND PANEL. |
| |
| THIS IS JUST A NOTE, IF A MAIN DISC IS |
| INSTALLED OUTSIDE, A MCB IS NOT REQ`D IN |
| SIDE. |
| |
| 7)NOTE: PLEASE SEE WASHER RECEPT SHOWN |
| AS GFI? THIS IS TO BE A SINGLE RECEPT |
| AND NOT TO BE GFI. |
| PLEASE CLARIFY WHERE THE LAUNDRY RECEPT |
| SHOWN ON PANEL SCHEDULE IS? |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |