2003-06-20 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SEE NOTES TO ELEC.
 WORK PER PALM BEACH COUNTY. PLEASE NOTE,
 CITY OF WEST PALM BEACH.
  
 2)NOTE: PLEASE SEE 210-52D/210-11C3,
 DEDICATED BATH(S) CIRCUITS REQ`D TO BE
 #12 AWG, AND 20A.
  
 3)NOTE: PLEASE CLARIFY WASHER/LAUNDRY,
 WASHER SHOWN AT 1.2KW(1.5REQ`D) BUT
 LAUNDRY RECEPT SHOWN AT 1.5KW?
 WHICH ONE?
  
 4)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW SERVICE EQUIPMENT. 110-9,215-5
 MAINS/PANELS/BRKRS ARE ALL TO RATED FOR
 THE AVAILABLE FAULT CURRENT.
  
 5)NOTE:PLEASE SEE FS/FAC PLANS CONTAIN-
 -ING A TITLE BLOCK, MUST BE SIGNED,
 DATED AND SEALED BY THE ARCH/ENGINEER OF
 RECORD. 471.025/184.221
  
 6)NOTE: PLEASE SEE 250-110,250-122, FOR
 EQUIPMENT GROUNDING CONDUCTOR BETWEEN
 MAIN AND PANEL.
  
 THIS IS JUST A NOTE, IF A MAIN DISC IS
 INSTALLED OUTSIDE, A MCB IS NOT REQ`D IN
 SIDE.
  
 7)NOTE: PLEASE SEE WASHER RECEPT SHOWN
 AS GFI? THIS IS TO BE A SINGLE RECEPT
 AND NOT TO BE GFI.
 PLEASE CLARIFY WHERE THE LAUNDRY RECEPT
 SHOWN ON PANEL SCHEDULE IS?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  