2003-07-14 00:00:00 | ******CORRECTIONS****** |
| |
| 1.SIGN THE OWNER/AGENT LINE OF THE |
| ENERGY CALC. |
| |
| 2.)SHEET 1, STORM PROTECTION AND |
| GARAGE DOOR NOTES SAY PALM BEACH COUNTY |
| AMENDMENTS.IT SHOULD STATE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| |
| 3.)THE RED HEAD ATTACHMENT SCHEDULE |
| FOR THE GARAGE DOOR BUCK CONFLICTS |
| WITH THE PRODUCT APPROVAL (SHEET 1). |
| |
| 4.)WINDOW L2 AT BOTH BATH TUBS ARE |
| REQUIRED TO COMPLY WITH FBC2405.1. |
| |
| 5.)ON THE TYPICAL WALL SECTION (SHEET |
| 1) AND MONOLITHIC WALL FOOTING (SHEET 3) |
| SHOW THE 4" ABOVE GRADE AND 12" BELOW |
| GRADE MINIMUMS (FBC1804.1.3, CITY OF |
| WPB AMENDMENTS TO THE FBC1804.1.7). |
| |
| 6.)FIRESTOP REQUIRED, FBC 705.3. |
| |
| 7.)PROVIDE A SOILS INVESTIGATION |
| REPORT, CITY OF WEST PALM BEACH AMEND. |
| TO THE FBC1804.2.2. |
| |
| 8.)SHOW THE SIZE OF THE ATTIC ACCESS; |
| COMPLY WITH FBC2309.6. |
| |
| 9.)SEPARATE PERMITS REQUIRED. |
| |
| 10.) BEFORE A PERMIT CAN BE ISSUED, |
| IMPACT FEES MUST BE PAID TO PALM BEACH |
| COUNTY.THE PLANS MUST BE STAMPED AND |
| THE ORIGINAL RECEIPT ATTACHED TO THE |
| APPLICATION.233-5025 |
| |
| 11.) PLEASE DO NOT STAPLE THE PRODUCT |
| APPROVALS TO THE PLANS AS THEY MAKE |
| THE PLAN AND THE PAS DIFFICULT TO READ. |
| |
| 12.)PROVIDE A HURRICANE SHUTTER |
| ATTACHMENT SCHEDULE. |
| |
| 13.)A NOTICE OF COMMENCEMENT MUST |
| BE FILED WITH THE CLERK OF COURTS BEFORE |
| A PERMIT CAN BE ISSUED. |
| |
| 14.)ADDITIONAL FEES DUE, $177.44. |
| |
| 15.)GORDON F. BUCK HAS CERTIFIED THE |
| DESIGN OF THE TRUSS CONNECTIONS (SHEET |
| 4), BUT KARPINIA IS THE CONSULTING |
| ENGINEER ON THE JOB.PLEASE ADDRESS. |
| |
| 16.)SHOW THE LATERAL BRACING IN THE |
| ROOF NOTES (SHEET 4) ON THE ROOF FRAMING |
| PLAN. |
| |
| 17.)SIMPSON 2003 CATALOG SPECIFIES |
| A DIFFERENT NAILING SCHEDULE (NUMBER AND |
| SIZE) FOR THE HETAL16 TRUSS CONNECTOR. |
| EITHER REVISE YOUR SCHEDULE TO BE |
| CONSISTENT WITH THE CATALOG OR PROVIDE |
| CALCULATIONS TO SHOW HOW THIS CONNECTOR |
| WILL OBTAIN THE 1000# UPLIFT.ALSO |
| DO THE SAME WITH H3 AND ANY OTHER |
| CONNECTORS ON THE PLAN WHICH HAVE EITHER |
| A DIFFERENT NUMBER OF NAILS SPECIFIED |
| OR A DIFFERENT TYPE NAIL SPECIFIED THAN |
| THE CATALOG. |
| |
| 18.) SHOW THE CONNECTOR LOCATIONS ON |
| THE ROOF FRAMING PLAN (SHEET 4). |
| |
| 19.) PROVIDE PRODUCT APPROVALS FOR THE |
| SLIDING GLASS DOOR. |
| |
| WHEN RESUBMITTING, REPLACE SHEETS WHICH |
| HAVE CHANGED WITH THE NEW SHEETS. SUBMIT |
| THE OLD SHEETS SEPARATELY MARKED "VOID". |
| CLEARLY MARK ALL CHANGES WITH CLOUDS OR |
| TRIANGLES. |
| |
| SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| [email protected] |