Plan Review Notes
Plan Review Notes For Permit 03060647
Permit Number 03060647
Review Stop B
Sequence Number 1
Notes
Date Text
2003-07-10 00:00:00******CORRECTIONS*******
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC, FBC 13-103.1.2.
  
 4.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE ORIGINAL RECEIPT
 ATTACHED TO THE APPLICATION.
  
 5.)GENERAL NOTES, A1, VISQUEEN IS
 REQUIRED TO BE .006 MIN, NOT .004,
 FBC APPENDIX B, 302.
  
 6.)1 1/2" WATERSTOP IS REQUIRED, NOT
 3/4" AS SHOWN ON THE PLAN, CITY OF
 WEST PALM BEACH AMENDMENTS TO THE FBC,
 2111.1.9.REVISE ALL AFFECTED NOTES,
 INCLUDING 3-A2, FOUNDATION NOTE #12 A2,
 1-A4, 2-A4.
  
 7.)THE FOOTING IS REQUIRED TO BE 4"
 MIN. ABOVE GRADE, 12" MIN. BELOW GRADE
 (FBC1804.1.3 AND CITY OF WPB AMENDMENTS
 TO THE FBC 1804.1.7).REVISE ALL
 AFFECTED NOTES AND DETAILS, INCLUDING
 3-A2, 1-A2, 1-A4, 2-A4.
  
 8.)REVISE THE PERMIT APPLICATION TO
 REFLECT THE SCOPE OF WORK.IT NOW SAYS
 ONLY "DEMO INTERIOR".
  
 9.) HAVE THE DESIGNER READ THE SOILS
 REPORT PROVIDED WITH THIS PERMIT
 APPLICATION.
  
 A.) THE PLANS REFER TO "VIBRO
 COMPACTED" TO PREPARE THE SOIL.THIS
 IS IN CONFLICT WITH THE SOILS REPORT.
 REVISE ALL NOTES AND DETAILS, INCLUDING
 FOUNDATION NOTE #2 A2, 3-A2, GENERAL
 NOTEA1.
  
 B.) PRESSURE GROUTING OF THE EXISTING
 AND PROPOSED FOUNDATIONS ARE REQUIRED.
 MAKE A NOTE ON THE PLAN.
  
 10.)THE 24 SINGLE HUNG WINDOWS DO NOT
 COMPLY WITH FBC1005.4.
  
 11.)THE 2'6 DOOR (BATHROOM) DOES NOT
 COMPLY WITH FBC 11-11 (2'8" MINIMUM).
  
 12.)THE AREA CALCS, A1, SHOULD SHOW
 EXISTING CONDITIONED AND UNCONDITIONED
 SPACE, PROPOSED NEW, AND TOTALS.
  
 13.)PROVIDE A SURVEY FOR THIS JOB.
  
 14.)WIND INFILTRATION, A5, INTERNAL
 PRESSURE COEFFICIENT IS SHOWN AS 1.0.
 IS THIS NUMBER CORRECT?ALSO GIVE THE
 APPLICABLE ENCLOSURE CLASSIFICATION
 FBC1606.1.7.
  
 15.)THE TEXT FOR 1005.4, A5, APPEARS
 TO BE FROM A CODE OTHER THAN FBC. EITHER
 MAKE THE TEXT CONSISTENT WITH THE
 CURRENT BUILDING CODE OR REMOVE IT FROM
 THE PLAN.
  
 16.)IMPACT PROTECTION IS REQUIRED FOR
 THE GLAZED DOOR, FBC 1606.1.4.PROVIDE
 TWO COPIES OF PRODUCT APPROVALS.
  
 17.)THE FOOTING WIDTH SHOULD BE A
 MINIMUM OF 18" PER THE SOILS REPORT.
 REVISE ALL NOTES AND DETAILS, INCLUDING
 1-A2, 3-A2, 1-A4, 2-A4.
  
 18.)SUBMIT PRODUCT APPROVALS FOR:
 MULLIONS
 SINGLE HUNG WINDOW (PAS SUBMITTED
 WERE ILLEGIBLE)
 IMPACT PROTECTION FOR THE DOOR
 ROOF SHINGLES (MAY BE SUBMITTED NOW
 OR WITH ROOF PERMIT APPLICATION)
 LOUVERED GABLE VENT
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]