2003-07-10 00:00:00 | ******CORRECTIONS******* |
| |
| 1.)SEPARATE PERMITS REQUIRED. |
| |
| 2.)A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3.)SIGN THE OWNER/AGENT LINE OF THE |
| ENERGY CALC, FBC 13-103.1.2. |
| |
| 4.)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY.THE PLANS MUST BE |
| STAMPED AND THE ORIGINAL RECEIPT |
| ATTACHED TO THE APPLICATION. |
| |
| 5.)GENERAL NOTES, A1, VISQUEEN IS |
| REQUIRED TO BE .006 MIN, NOT .004, |
| FBC APPENDIX B, 302. |
| |
| 6.)1 1/2" WATERSTOP IS REQUIRED, NOT |
| 3/4" AS SHOWN ON THE PLAN, CITY OF |
| WEST PALM BEACH AMENDMENTS TO THE FBC, |
| 2111.1.9.REVISE ALL AFFECTED NOTES, |
| INCLUDING 3-A2, FOUNDATION NOTE #12 A2, |
| 1-A4, 2-A4. |
| |
| 7.)THE FOOTING IS REQUIRED TO BE 4" |
| MIN. ABOVE GRADE, 12" MIN. BELOW GRADE |
| (FBC1804.1.3 AND CITY OF WPB AMENDMENTS |
| TO THE FBC 1804.1.7).REVISE ALL |
| AFFECTED NOTES AND DETAILS, INCLUDING |
| 3-A2, 1-A2, 1-A4, 2-A4. |
| |
| 8.)REVISE THE PERMIT APPLICATION TO |
| REFLECT THE SCOPE OF WORK.IT NOW SAYS |
| ONLY "DEMO INTERIOR". |
| |
| 9.) HAVE THE DESIGNER READ THE SOILS |
| REPORT PROVIDED WITH THIS PERMIT |
| APPLICATION. |
| |
| A.) THE PLANS REFER TO "VIBRO |
| COMPACTED" TO PREPARE THE SOIL.THIS |
| IS IN CONFLICT WITH THE SOILS REPORT. |
| REVISE ALL NOTES AND DETAILS, INCLUDING |
| FOUNDATION NOTE #2 A2, 3-A2, GENERAL |
| NOTEA1. |
| |
| B.) PRESSURE GROUTING OF THE EXISTING |
| AND PROPOSED FOUNDATIONS ARE REQUIRED. |
| MAKE A NOTE ON THE PLAN. |
| |
| 10.)THE 24 SINGLE HUNG WINDOWS DO NOT |
| COMPLY WITH FBC1005.4. |
| |
| 11.)THE 2'6 DOOR (BATHROOM) DOES NOT |
| COMPLY WITH FBC 11-11 (2'8" MINIMUM). |
| |
| 12.)THE AREA CALCS, A1, SHOULD SHOW |
| EXISTING CONDITIONED AND UNCONDITIONED |
| SPACE, PROPOSED NEW, AND TOTALS. |
| |
| 13.)PROVIDE A SURVEY FOR THIS JOB. |
| |
| 14.)WIND INFILTRATION, A5, INTERNAL |
| PRESSURE COEFFICIENT IS SHOWN AS 1.0. |
| IS THIS NUMBER CORRECT?ALSO GIVE THE |
| APPLICABLE ENCLOSURE CLASSIFICATION |
| FBC1606.1.7. |
| |
| 15.)THE TEXT FOR 1005.4, A5, APPEARS |
| TO BE FROM A CODE OTHER THAN FBC. EITHER |
| MAKE THE TEXT CONSISTENT WITH THE |
| CURRENT BUILDING CODE OR REMOVE IT FROM |
| THE PLAN. |
| |
| 16.)IMPACT PROTECTION IS REQUIRED FOR |
| THE GLAZED DOOR, FBC 1606.1.4.PROVIDE |
| TWO COPIES OF PRODUCT APPROVALS. |
| |
| 17.)THE FOOTING WIDTH SHOULD BE A |
| MINIMUM OF 18" PER THE SOILS REPORT. |
| REVISE ALL NOTES AND DETAILS, INCLUDING |
| 1-A2, 3-A2, 1-A4, 2-A4. |
| |
| 18.)SUBMIT PRODUCT APPROVALS FOR: |
| MULLIONS |
| SINGLE HUNG WINDOW (PAS SUBMITTED |
| WERE ILLEGIBLE) |
| IMPACT PROTECTION FOR THE DOOR |
| ROOF SHINGLES (MAY BE SUBMITTED NOW |
| OR WITH ROOF PERMIT APPLICATION) |
| LOUVERED GABLE VENT |
| |
| SAMANTHA THYNG, BUILDING PLANS EXAMINER |