Plan Review Notes
Plan Review Notes For Permit 03060594
Permit Number 03060594
Review Stop E
Sequence Number 2
Notes
Date Text
2003-09-18 00:00:00*********** UNSAT ******************
  
 1)NOTE: PLEASE SEE THAT NOW A NEW SET
 OF ELECTRICAL PLANS ARE NOW BEING
 SUBMITTED FROM A DIFFERENT ARCH.
 PLEASE SEE THAT THERE WAS INFORMATION
 ON OLD SHEETS NOT ON NEW? ONLY ONE SET
 OF ELECTRICAL PLANS MAY BE SUBMITTED
 BY ONE ARCH. PLEASE REMOVE OLD SHEETS.
  
 2)NOTE: PLEASE SUBMIT A PANEL SCHEDULE
 AND CORRELATE CIRCUITING ON PLANS.
  
 3)NOTE: PLEASE SEE 210.62 FOR MISSING
 SHOW WINDOW RECEPTS..
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE REMOVE OLD/VOIDED SHEETS
 AND HAVE TWO CLEAN SETS FOR REVIEW
 AND STAMPING. ONE SET/COPY OF OLD SHEETS
 MAY BE SUBMITTED FOR REFERENCE UNATTACH-
 ED TO NEW SETS.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 PERMIT APPLICATION HAS COME IN W/OUT
 ANY SUITE #??
 PLEASE ALSO SEE THAT PLANS ARE REQ'D
 UNDER FAC/FS 61G1-16.004, 481 TO HAVE
 COMPLETED ADDRESS ON TITLE BLOCK FOR
 JOB.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW . IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]