Plan Review Notes
Plan Review Notes For Permit 03060594
Permit Number 03060594
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-07-08 00:00:001) REFLECTED CEILING PLAN DOES NOT
 INDICATE ANY EMERGENCY LIGHTING
 EQUIPMENT.
  
 2) NO INTERIOR FINISH CLASSIFICATION
 PROVIDED FOR WALLS AND CEILINGS.
  
 3) PLEASE INDICATE SCOPE OF FIRE
 SPRINKLER REMODEL. WILL THERE BE
 ANY MODIFICATIONS TO THE FS SYSTEM.
  
 4) IS THERE ANY EXISTING OR NEW FIRE
 ALARM EQUIPMENT PLANNED WITHIN
 SPACE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910