2004-03-22 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| |
| 1) FROM PREVIOUS REVIEWS: SHT A-2 CON- |
| CESSIONS FOOD SERVICE. PLEASE CONTACT |
| THE PALM BEACH HEALTH UNIT, 901 EVERNIA |
| ST. WPB FOR REVIEW PRIOR TO SUBMITTING |
| PLANS FOR REVIEW. PLANS SHALL BE STAMPED |
| BY THE PBC HEALTH UNIT. SECTION 101.4.7 |
| RESPONSE STATES "SEE ATTACHED STAMPED |
| DRAWINGS FROM THE PBC HEALTH UNIT, BUT |
| I CANNOT FIND STAMPED PLANS. BE SPEFIC |
| WITH RESPONSES AND INDICATE WHERE THE |
| STAMP IS LOCATED. I HAVE LOOKED AND BOTH |
| FRONT AND BACK OF ALL SHEETS ON AT LEAST |
| TWO SETS. ALL SETS SHALL BE STAMPED. |
| 2) FROM PREVIOUS REVIEWS: SIZE GUTTERS |
| PER TABLE 1106.6. 5" GUTTERS @ 1/4" |
| SLOPE CAN ONLY HAVE A MAXIMUM OF 1111 SQ |
| FT. AND CALCULATIONS INDICATE 3481 TO EA |
| DOWNSPOUT. AT 1/4" THE GUTTER WILL BE |
| REQUIRED TO BE 8" MINIMUM. SHOW SLOPE |
| OF GUTTER - INDICATE WHERE THE HIGH |
| POINTS OF THE GUTTER AND SHOW THIS SLOPE |
| ON THE GUTTER ON THE PLANS. |
| 3) PER RESPONSE FROM RODNEY COMPO, A |
| SAMPLE POINT SHALL BE REQUIRED ON THE |
| LINE TO THE CONCESSION STAND. SHOW THE |
| SAMPLE ON BOTH THE FLOOR PLAN, (SHT P-2) |
| AND THE SANT. RISER DIAG., (SHT P-3). |
| |
| REVIEW BY KEN STEVENS |