Plan Review Notes
Plan Review Notes For Permit 03060499
Permit Number 03060499
Review Stop P
Sequence Number 3
Notes
Date Text
2004-03-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) FROM PREVIOUS REVIEWS: SHT A-2 CON-
 CESSIONS FOOD SERVICE. PLEASE CONTACT
 THE PALM BEACH HEALTH UNIT, 901 EVERNIA
 ST. WPB FOR REVIEW PRIOR TO SUBMITTING
 PLANS FOR REVIEW. PLANS SHALL BE STAMPED
 BY THE PBC HEALTH UNIT. SECTION 101.4.7
 RESPONSE STATES "SEE ATTACHED STAMPED
 DRAWINGS FROM THE PBC HEALTH UNIT, BUT
 I CANNOT FIND STAMPED PLANS. BE SPEFIC
 WITH RESPONSES AND INDICATE WHERE THE
 STAMP IS LOCATED. I HAVE LOOKED AND BOTH
 FRONT AND BACK OF ALL SHEETS ON AT LEAST
 TWO SETS. ALL SETS SHALL BE STAMPED.
 2) FROM PREVIOUS REVIEWS: SIZE GUTTERS
 PER TABLE 1106.6. 5" GUTTERS @ 1/4"
 SLOPE CAN ONLY HAVE A MAXIMUM OF 1111 SQ
 FT. AND CALCULATIONS INDICATE 3481 TO EA
 DOWNSPOUT. AT 1/4" THE GUTTER WILL BE
 REQUIRED TO BE 8" MINIMUM. SHOW SLOPE
 OF GUTTER - INDICATE WHERE THE HIGH
 POINTS OF THE GUTTER AND SHOW THIS SLOPE
 ON THE GUTTER ON THE PLANS.
 3) PER RESPONSE FROM RODNEY COMPO, A
 SAMPLE POINT SHALL BE REQUIRED ON THE
 LINE TO THE CONCESSION STAND. SHOW THE
 SAMPLE ON BOTH THE FLOOR PLAN, (SHT P-2)
 AND THE SANT. RISER DIAG., (SHT P-3).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]