Plan Review Notes
Plan Review Notes For Permit 03060499
Permit Number 03060499
Review Stop B
Sequence Number 3
Notes
Date Text
2004-03-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03060499
 ADD: 4017 PINEWOOD AVENUE
 CONT: PLAN REVIEW- TBA
 CONTACT: JEFF HALVERSON
 TEL: (561)659-8040
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PROVIDE A UNITY OF TITLE FOR LOTS
 20,22,24.1, 24.2,24.3 AND THE ABANDOMENT
 OF THE RIGHT OF WAY FOR 40TH STREET.
 THE ACTUAL ENTRY MAY BE OFF THE PROPERTY
 AND IN THE RIGHT OF WAY. SHEET LS1 SHOWS
 A ASSUMED PROPERTY LINE BUT NO "ACTUAL
 PROPERTY LINE". THE ASSUMED PROPERTY
 LINE INDICATED FOR THE NORTH SIDE OF THE
 BUILDING IS RIGHT AGAINST THE GAZEBO
 INDICATE WHAT TYPE OF BLDG THIS WILL
 BE AND AMOUNT OF OPENINGS TO COMPLY
 WITH TABLE 600!!!!!!!!!!!!!!!!!!!!
  
 2) THE UNITY OF TITLE TO BE RECORDED AT
 THE CLERK OF THE COURT AS WELL AS THE
 PROPERTY APPRAISERS OFFICE.
  
 3A)SHEET 4.1 WEST ELEVATION 4'-0" DIA.
 FIXED WINDOWS SHALL BE 45 MINUTE OPENING
 PROTECTIVES, 705.1.1.2.COMMENTS INDICATE
 45 MIN. SEE WINDOW SCHEDULE A8.
  
 3B)SHEET A2.1 INDICATE DOOR OPENING
 NUMBER 126 WHICH HAS A LOUVER, 705.1.1.2
 WILL REQUIRE A 45 MINUTE PROTECTIVE.
  
 3C) DISCREPANCY SEE SOUTH SERVICE YARD
 SHEET A2 INDICATES DOOR# 110 14'-6" FROM
 THE PROPERTY LINE VS A2.2> 15'. MAY
 REQUIRE OPENING PROTECTIVES FOR LOUVER
 IF < 15'-0".
  
 4) SINCE THERE IS NO ESTABLISHED PROPER-
 TY LINE ON THE NORTH PROPERTY LINE,
 THIS SAME ISSUE, OPENING PROTECTIVES
 WILL BECOME A ISSUE. SEE COMMENT # 1.
 3A & 3B.
  
 5) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL I
 S NOT DEFINITEY KNOWN, OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL P
 ROPERLY LICENSED IN THE STATE OF
 FLORIDA.
 *****PROVIDE SIGNED & SEALED REPORTS (3)
  
 6) PROVIDE FIRE SPRINKLER PLANS REQUIRED
 BY TABLE 500 ALLOWED AREA INCREASE FOR
 SPRINKLERED BUILDINGS AND 903.7.2.4.
 PROVIDE (3) COPIES.
  
 7) SHEET A2 INDICATES ADA FOR 2 WHEEL-
 CHAIRS. THE PLANS DO NOT INDICATE WHERE
 THE COMPANION SEATING IS LOCATED AS
 REQUIRED IN 11-4.6(3)(F)(I).
  
 8) PLANS DO NOT INDICATE ANY LIFT TO
 ACCOMPLISH VERTICAL ACCESSIBILITY TO
 BLEACHERS A WAIVER REQUEST TO BE SUBMIT-
 TED TO THE STATE IF A LIFT AND COMPANION
 SEATING NOT PROVIDED TO ALL LEVELS.
 11-4.1.2 VERTICAL ACCESSIBILITY,
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 SSTRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIAABLE
 GRADE LEVEL.
  
 9) MENS RESTROOM# 117 DOOR LEADING INTO
 THE HANDICAPPED STALL REQUIRES 1'-0"
 FROM THE LATCH SIDE.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 10) DOOR 6/123 ALSO REQUIERES 18" ON
 THE PULL SIDE.
  
 11) ACCESSIBLE ELEMENTS & SPACES
 11-4.30 SIGNAGE PROVIDE REQUIRED SIGNAGE
 FOR ALL ACCESIBLE AREAS, 1-6.
 11-4.30.7 SYMBOLS OF ACCESSIBILITY SHALL
 USE THE INTERNATIONAL SYMBOL OF ACCESS-
 IBILITY.
  
 12) S-3 STRUCTURAL NOTES: WIND LOADS
 CORRECT 1997 SBC TO 2001 FLORIDA BUILD-
 ING CODE ND THE WIND ZONE IS 140 MPH,
 3 SECOND GUST.
  
 13) CORRECT PROJECT DESIGNED UNDER THE
 1997 SBC.
  
 14) DOOR SCHEDULE DOESN'T INDICATE WHAT
 DOORS REQUIRE PUSH BAR PANIC HARDWARE
 NOR DOES THE SCHEDULE INDICATE HANDI-
 CAPPED ACCESSIBLE HARDWARE THE SUPPLIED
 HARDWARE SPECIFICATION LIST 14 TYPES OF
 DOORS NOT IDENTIED TO THE PLANS?
  
 15) MISSING THE ATTACHED DETAIL FOR THE
 BLEACHERS AS ASKED FOR BY PREVIOUS
 REVIEWER.
  
 16) SHEET S-5 SECTION# 2 INDICATES THE
 USE OF A SIMPSON ST18 WELDED TO TUBE
 STEEL, SIMPSON STATES IN THEIR CATALOG
 PAGE 11, 2004 CAT. INSTRUCTIONS TO IN-
 STALLERS (F) UNLESS OTHERWISE NOTED
 SIMPSON CONNECTORS CANNOT BE WELDED.
 PRODUCE A SEALED LETTER FROM SIMPSONS
 P. E. STATING WHAT CONDITIONS IF ANY SIM
 PSON WILL ALLOW WELDING.
  
 17) STRUCTURAL PLANS INDICATE THE USE OF
 TRUSS ANCHORS BUT NO LOADS ARE GIVEN
 FOR THE CONNECTORS?
  
 18) COMMENT 13 FROM PREVIOUS REVIEW,
 THE NEW DETAIL MISSING THE WIRE SIZE,
 SPACING, NOR THE VERTICAL STUDS INDICATE
 ATTACHMENT TO THE STRUCTURE ABOVE?
  
 19) COMMENT 14 FROM PREVIOUS REVIEW,
 SHEET S4 MASONARY NOTE# 4, AND S3 MASON-
 ARY NOTE# 2 "STILL" DO NOT AGREE CORRECT
 THE S4 NOTE, 8" BLOCK CAN NOT HAVE BOTH
 VALUES.
  
 20) COMMENT 15 FROM PREVIOUS REVIEW,
 SHEET S4 CALLS OUT SSTD 12-97, THE FBC
 INVOKES 12-99. SEE FBC 35. THIS NOTE
 STILL NOT CHANGED!
  
 21)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED & OPERATIBLE
 B) DOORS,GLAZED SOLID AND LOUVERED
 C) LOUVERS
 D) ROOFING ASSEMBLIES, ALL TYPES USED
 E) TRUSS ANCHORS
 *****IMPORTANT******
 22)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGE CAN BE FOUND WILL HELP
 TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 (561)805-6715


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved