2004-02-13 00:00:00FAILED:
 1. PROPOSED SITE MUST BE DESIGNED FOR
 STORM WATER PER CITY OF WEST PALM BEACH
 REQUIREMENT AND CRITERIA, PLEASE SUBMIT
 CALCULATION FOR OUR REVIEW AND APPROVAL.
 2. SEWER LATERAL MUST BE AT MINIMUM 6"
 WHEN CONNECTING TO CITY SEWER MAIN, SEE
 STANDARD DETAILS ON SHEET C-3 OF 3.
 3. ALL CONNECTION TO CITY SERVICES MUST
 BE APPROVED BY PUBLIC UTILITIES AND
 ENGINEERING SERVICES 659-8040, ATT;MANNY
 GONZALEZ.
 4. EXISTING FIRE HYD. AS SHOWN ON SHEET
 C1 OF 3 SHOULD BE RLOCATED, PLEASE
 VERIFY.
  