Plan Review Notes For Permit 03060499 |
Permit Number |
03060499 |
|
Review Stop |
ENG |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-02-13 00:00:00 | FAILED: | | 1. PROPOSED SITE MUST BE DESIGNED FOR | | STORM WATER PER CITY OF WEST PALM BEACH | | REQUIREMENT AND CRITERIA, PLEASE SUBMIT | | CALCULATION FOR OUR REVIEW AND APPROVAL. | | 2. SEWER LATERAL MUST BE AT MINIMUM 6" | | WHEN CONNECTING TO CITY SEWER MAIN, SEE | | STANDARD DETAILS ON SHEET C-3 OF 3. | | 3. ALL CONNECTION TO CITY SERVICES MUST | | BE APPROVED BY PUBLIC UTILITIES AND | | ENGINEERING SERVICES 659-8040, ATT;MANNY | | GONZALEZ. | | 4. EXISTING FIRE HYD. AS SHOWN ON SHEET | | C1 OF 3 SHOULD BE RLOCATED, PLEASE | | VERIFY. | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | MOHAMMAD R. AMINI |
|