2004-02-17 00:00:00*********UNSAT ***********
  
 1)NOTE: PLEASE SEE THAT PLANS ARE ONLY
 IN FOR PLAN REVIEW AND NOT FOR PERMIT.
 THE STATE HAS ADOPTED THE 2002 NEC
 SINCE PLANS WERE REVIEWED LAST.
 PLEASE MAKE ANY ADJUSTMENTS AS NESS.
  
 2)NOTE: PLAN NOTE MENTIONS TO SEE SPECS
 FOR COLOR CODING OF CONDCUTORS.
 SPEC BOOKS DID NOT SEEM TO GET SUBMITTED
 FOR REVIEW.?
  
 3)NOTE: PLANS REF NOTE TO GROUND TRANS-
 -FORMERS PER 250.30. PLEASE GIVE THE
 ATTACHMENT(BLDG STEEL)(FOOTER STEEL)?
  
  
 4)NOTE: PLEASE PROVIDE ALL INFORMATION
 ON TITLE BLOCKS AS REQ'D UNDER FS 471
 AND FAC 61G15-23.002
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  