2004-02-25 00:00:00 | ****CORRECTIONS**** |
| |
| PAID PLAN REVIEW, NOT A PERMIT APP. |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)THIS WILL BE A THRESHOLD BUILDING |
| AS DEFINED IN FBC105.13 AND WILL REQUIRE |
| A THRESHOLD INSPECTOR AND A THRESHOLD |
| INSPECTION PLAN PRIOR TO PERMITTING. |
| |
| 2.)SOME SHEETS HAVE A PHOTOCOPY OF |
| A SEAL AND SIGNATURE.ALL SIGNATURES |
| ARE TO BE ORIGINAL WITH A RAISED SEAL. |
| THE PRINTED NAME AND LICENSE NUMBER OF |
| THE PERSON SEALING THE DOCUMENT IS TO |
| BE INCLUDED ON THE SHEET, FAC61G15-23, |
| FAC61G1-16.003, 004. |
| |
| 3.)PROVIDE A SOILS INVESTIGATION |
| REPORT. |
| |
| 4.)THE 3' DIMENSION ON A1.1 POINTS TO |
| A DIMENSION LINE THAT ENCROACHES THE |
| PROPERTY LINE.NOTE THAT A 3' SETBACK |
| FROM THE PROPERTY LINE WOULD REQUIRE A |
| 3 HR WALL AS PER TABLE 600.IT MUST BE |
| OVER 3' TO REQUIRE A 2 HR WALL AS |
| INDICATED ON THE PLAN.REVISE ALL |
| SHEETS NECESSARY TO REFLECT A DIMENSION |
| OF GREATER THAN 3', OR CHANGE THE |
| STRUCTURAL DETAILS TO COMPLY WITH |
| TABLE 600. |
| |
| 5.)REVISE THE BUILDING DATA, ITEM #3, |
| LS1 TO CORRECTLY REFLECT THE FIRE |
| RESISTANCE RATINGS. |
| |
| 6.)PRODUCT APPROVALS NOT SUBMITTED |
| BEFORE ISSUANCE OF THE PERMIT WILL |
| REQUIRE SEPARATE PERMITS WITH SEPARATE |
| FEES. |
| |
| 7.)SEE PREVIOUS LIST REGARDING THE |
| DOOR HARDWARE AND THE BLEACHERS.A |
| TRANSMITTAL LETTER REFERS TO A |
| SPECIFICATION SECTION AND BLEACHER |
| SECTION.I WAS UNABLE TO FIND THESE ON |
| THE PLAN.THE GYMNASIUM EQUIPMENT |
| SPECIFICATIONS PROVIDED DO NOT SHOW |
| COMPLIANCE WITH FBC1012 AND 1019.7 |
| (HARDWARE).PLEASE REVISE THE PLAN. |
| |
| 8.)COMPLIANCE WITH TABLE 600 SHOULD |
| BE INDICATED ON THE STRUCTURAL AND |
| ARCHITECTURAL SHEETS AS WELL AS LS1. |
| |
| 9.)LS1, PROVIDE THE DISTANCE TO THE |
| PROPERTY LINE FOR THE 1 HR WALL.PLANS |
| ARE TO BE TO SCALE, FBC104.2.1. |
| |
| 10.) PLEASE NOTE THAT THE UL LISTING |
| PROVIDED FOR THE 1 HR WALL (LS1) REFERS |
| TO U905, WHICH IS 2 HR.DETAILS WHICH |
| EXCEED CODE REQUIREMENTS ARE |
| ACCEPTABLE; THIS NOTE IS ADVISORY ONLY. |
| |
| 11.)HETAL16, 3-S5, FASTENING CONFLICTS |
| WITH CATALOG.USE HIGH-WIND CATALOG |
| WHICH INCLUDES UPDATED LOADS RELATED TO |
| STRESS INCREASES FOR STEEL, AND CHECK |
| ALL CONNECTORS.CALCULATIONS FOR THE |
| ALTERNATE FASTENING MAY BE SUBMITTED IN |
| LIEU OF CHANGING THE PLAN. |
| |
| 12.)WHEN RESUBMITTING, PLEASE SUBMIT |
| OLD SHEETS SEPARATELY FOR REFERENCE. |