Plan Review Notes For Permit 03060499
Permit Number 03060499
Review Stop P
Sequence Number 1
Notes
Date Text
2003-06-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 AMENDMENTS TO FBC, CHAPTER 1,
 ADMIN. CODE.
  
 1) SHT- LS1, 2001 PLUMBING CODE MINIMUM
 FIXTURE CALCULATIONS. 9 WATER CLOSETS
 ARE REQUIRED. SHOWS ONLY 7 PROVIDED.
 TABLE 403.1
 2) SHT A-2 CONCESSIONS FOOD SERVICE.
 PLEASE CONTACT PALM BEACH COUNTY HEALTH
 UNIT 901 EVERNIA STREET WPB FOR REVIEW
 PRIOR TO RESUBMITTING PLANS WITH THE
 CITY FOR REVIEW. (561) 355-3018
 SECTION 101.4.7
 3) CONTACT RODNEY COMPO - INDUSTRIAL
 PRE-TREATMENT, ENVIRONMENTAL COMPLIANCE
 TO DETERMINE THE SIZE OF GREASE TRAP RE-
 QUIRED.
 4) SHTS A2 & A5 TURNING CIRCLE REQUIRED
 IN TOILET ROOM NOT HDCP STALL. SECTION
 11-4.22.3
 5) SHT A10 DETAIL #3 SHOW URNAL HEIGHT
 11-18.2, AND CLEAR FLOOR SPACE 11-4.18.3
 6) SHT A10 SHOWER DETAILS REQUIRED. SEC
 11-4.21. SHOW GRAB BAR HEIGHT 4-21.4,
 CONTROLS 4.21.5, CURBS 4.21.7 ECT.
 7) SHT P-1 PLUMBING NOTES #1, & #2, FBC
 NOT STANDARD CODE IS IN EFFECT. PLEASE
 CHANGE REFERENCE.
 8) SHT P-1 PLUMBING NOTES #5, AIR CHAMB-
 ERS NOT APPROVED. DELETE FROM REFERENCE.
 9) SHT P-1 PLUMBING NOTES #10 RPZ BACK-
 FLOW REQUIRED. 608.13.2
 10) SHT P-1 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL REQUIRED. 607.3.2
 11) SHT P-2 ROOF CALCULATIONS FOR RD-2,
 SHT A-3 INDICATES 38'X 6' (1/2 OF 12'
 HEIGHT) = 228 SQ.FT., PLUS 38'X.75 FOR
 THE PARAPET = 28'6". TOTAL 256'6". NOT
 SHOWN IN CALCULATIONS IS THE 1/2 THE
 AREA OF THE VERTICAL WALL, AND THE AREA
 OF THE ROOF THAT DRAINS DOWN TO RD-2
 FROM THE EAST ENTRY PORCH. THIS IS TYPI-
 CAL FOR RD-3, AND RD-4. PLEASE CLAIRFY.
 SHOW THIS INFORMATION FOR THESE AREAS
 FOR ROOF DRAINS IN QUESTIONS.
 12) PROVIDE A STORM RISER DIAGRAM PER
 SECTION 104.2.1
 13) SUBMIT CALCULATIONS FOR THE MAIN
 GYM ROOF AREA. SIZE GUTTERS PER TABLE
 1106.6, SHOW SLOPE OF GUTTER. INDICATE
 NUMBER OF DOWNSPOUTS. (SHT A4.1 SHOWS
 ONLY ONE DOWNSPOUT) SHOW SIZE OF DOWN-
 SPOUT.TABLE 1106.2
 14) SHT P-3 DETAIL #4 WATER ROSER DIA-
 GRAM, AIR CHAMBERS ARE NOT APPROVED. DE-
 LETE FROM RISER DIAGRAM. 604.9
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692