2003-06-18 00:00:00 | 1) PLEASE REF NFPA 101 LIFE SAFETY CODE | | 2000 EDITION CHAPTER 12 AND NFPA 13 1999 | | EDITION. ( NFPA 13 SECTION 5-13.8 ) | | | | 2) MAXIMUM TRAVEL DISTANCE IS 200' NOT | | 250' (NFPA 101 ). | | | | 3) WHAT IS THE INTERIOR FINISH | | CLASSIFICATION FOR THE WALLS AND | | CEILING. | | | | 4) COULD NOT LOCATE FDC AND ITS | | RELATIONSHIP TO A FIRE HYDRANT WTHIN 150 | | FEET. | | | | 5) SEPARATE PLAN AND PERMIT APPLICATION | | IS REQUIRED FOR FIRE ALARM SYSTEM. | | (CLASS A OR FULLY ADDRESSABLE) | | | | 6) SEPARATE PLAN AND PERMIT APPLICATION | | IS REQUIRED FOR FIRE SPRINKLER SYSTEM. | | ( FLOW DATA) | | | | NATE MCCRAY, CAPTAIN | | 805-6722 OR 835-2910 |
|