Plan Review Notes For Permit 03060499 |
Permit Number |
03060499 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-06-18 00:00:00 | **************** UNSAT ************* | | | | PLEASE SEE FIRE REVIEW COMMENTS THAT | | MAY HAVE AN AFFECT ON ELECTRICAL PLANS. | | | | 1)NOTE: PLEASE CLARIFY GROUNDING OF | | TRANSFORMER PER 250-30 | | | | 2)NOTE:PLEASE INCLUDE THE REQ`D FOOTER | | STEEL IN GROUNDINGNOTE. 250-50 | | NOTE MENTIOND BLDG STEEL WHICH CAN BE | | DIFFERENT. | | | | 3)NOTE: PLEASE PROVIDENOTE AS TO COLOR | | CODING OF FEEDERS PER LOCAL AMENDMINS | | 210-5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. PLANS ARE IN GOOD SHAPE W/ MINOR | | ITEMS NEEDED. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|