Plan Review Notes
Plan Review Notes For Permit 03060499
Permit Number 03060499
Review Stop E
Sequence Number 1
Notes
Date Text
2003-06-18 00:00:00**************** UNSAT *************
  
 PLEASE SEE FIRE REVIEW COMMENTS THAT
 MAY HAVE AN AFFECT ON ELECTRICAL PLANS.
  
 1)NOTE: PLEASE CLARIFY GROUNDING OF
 TRANSFORMER PER 250-30
  
 2)NOTE:PLEASE INCLUDE THE REQ`D FOOTER
 STEEL IN GROUNDINGNOTE. 250-50
 NOTE MENTIOND BLDG STEEL WHICH CAN BE
 DIFFERENT.
  
 3)NOTE: PLEASE PROVIDENOTE AS TO COLOR
 CODING OF FEEDERS PER LOCAL AMENDMINS
 210-5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLANS ARE IN GOOD SHAPE W/ MINOR
 ITEMS NEEDED. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]