2004-02-13 00:00:00 | ************* UNSAT ************ |
| |
| 1)NOTE: PLEASE SEE PLANS, HAND DRAWN |
| CHANGES HAVE BEEN MADE TO PLANS. PLANS |
| CONTAIN WHITE-OUT. |
| PLANS MUST BE REPRINTED AND AND THEN |
| SIGNED, DATED AND SEALED BY THE ENGINEER |
| OF RECORD. |
| PREVIOUSLY NOTED. |
| |
| 2)NOTE: PLEASE HAVE PLANS "SIGNED" BY |
| THE ENGINEER WITH A COMPLETE "SIGNATURE" |
| AS REQ'D UNDER FS 471.025 AND FAC 61G15- |
| -23.002. PER RULING OF FBPE'S IN OCT 03, |
| INITIALS ARE NOT ACCEPTABLE UNLESS |
| PE LICENSE FROM STATE WAS SIGNED LIKE |
| THIS. IF WHAT APPEARS TO BE INITIALS |
| ARE INDEED "SIGNATURE" PLEASE PROIDE |
| COPY OF FL PE LICENSE AND DRIVERS LIC., |
| CONTAINING SIGNATURE. |
| |
| 3)NOTE: PLEASE SEE SD NOTE: ON E-1, |
| DOES NOT SEEM TO CORRELATE WITH PLANS |
| AND CIRCUITING. |
| PLEASE SEE NFPA-72 8-1.4.2, SD' THAT |
| ARE W/IN 20' OF COOKING APPLIANCE MUST |
| BE EQUIPPED WITH AN ALARM SILENCING |
| MEANS OR OF THE PHOTOELECTRIC TYPE. |
| |
| 4)NOTE: PLEASE CORRELATE LOADS SHOWN |
| FOR A/C. PANEL SHOWS ONE AND LOAD CALCS |
| SHOW ANOTHER. |
| PLEASE CLARIFY NO A/C IN OTHER UNIT?? |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |