2003-12-09 00:00:00************* UNSAT ************
  
 1)NOTE: PLEASE SEE THAT HAND DRAWN/
 WRITTEN CHANGES MUST BE REPRINTED AND
 THEN PLANS ARE TO BE SIGNED AND SEALED.
 PLEASE ALSO NOTE, PLANS ARE REQ'D TO
 HAVE A SIGNATURE. FS 471.025 AND FAC
 61G15-23.002. PLEASE NOTE: THIS OFFICE
 HAS BEEN INFORMED BY THE BOARD OF PE'S
 THAT SIGNATURE MUST CONTAIN A MIN OF
 FIRST AND LAST NAME. INITIALS ARE NOT
 PERMITTED.
  
 2)NOTE: PLEASE REDO LOAD CALCULATIONS.
 LOADS ARE DIFFERENT ON EACH AND YET
 COME UP WITH THE SAME LOAD??
  
 PLEASE SEE THAT THIS IS REQ'D ON ALL
 SHEETS WEATHER OR NOT A COMMENT FROM
 THE REVIEWER.
  
 PAEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  