Plan Review Notes For Permit 03060496 |
Permit Number |
03060496 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2003-12-09 00:00:00 | ************* UNSAT ************ | | | | 1)NOTE: PLEASE SEE THAT HAND DRAWN/ | | WRITTEN CHANGES MUST BE REPRINTED AND | | THEN PLANS ARE TO BE SIGNED AND SEALED. | | PLEASE ALSO NOTE, PLANS ARE REQ'D TO | | HAVE A SIGNATURE. FS 471.025 AND FAC | | 61G15-23.002. PLEASE NOTE: THIS OFFICE | | HAS BEEN INFORMED BY THE BOARD OF PE'S | | THAT SIGNATURE MUST CONTAIN A MIN OF | | FIRST AND LAST NAME. INITIALS ARE NOT | | PERMITTED. | | | | 2)NOTE: PLEASE REDO LOAD CALCULATIONS. | | LOADS ARE DIFFERENT ON EACH AND YET | | COME UP WITH THE SAME LOAD?? | | | | PLEASE SEE THAT THIS IS REQ'D ON ALL | | SHEETS WEATHER OR NOT A COMMENT FROM | | THE REVIEWER. | | | | PAEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|