2003-08-25 00:00:00******* UNSAT ************
  
 1)NOTE: PLEASE SEE ADDITIONAL LOAD
 CALCULATIONS SUBMITTED PER HAY VINH LY
 P.E. PLEASE SEE EXISTING SERVICE SHOWN
 AS 350A AND RISER DIAGRAM ON E-2 SHOWS
 600A. PLEASE VERIFY. SERVICE CONDUCTOR
 SIZE DOES NOT SEEM TO SUPPORT A 600A
 MAIN? PLEASE VERIFY ACTUAL FEEDER SIZE.
 310.16/215.5
  
 2)NOTE: PLEASE VERIFY SIZE OF HEAT FOR
 AHU'S, SHOWN AS 9.2 KW ON ELEC AND 8KW
 ON MECH? PLEASE CORRELATE.
  
 PLEASE SEE THAT MOST NOTES WERE ADDRESS-
 ED FROM FIRST REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  