Plan Review Notes For Permit 03060496 |
Permit Number |
03060496 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-08-25 00:00:00 | ******* UNSAT ************ | | | | 1)NOTE: PLEASE SEE ADDITIONAL LOAD | | CALCULATIONS SUBMITTED PER HAY VINH LY | | P.E. PLEASE SEE EXISTING SERVICE SHOWN | | AS 350A AND RISER DIAGRAM ON E-2 SHOWS | | 600A. PLEASE VERIFY. SERVICE CONDUCTOR | | SIZE DOES NOT SEEM TO SUPPORT A 600A | | MAIN? PLEASE VERIFY ACTUAL FEEDER SIZE. | | 310.16/215.5 | | | | 2)NOTE: PLEASE VERIFY SIZE OF HEAT FOR | | AHU'S, SHOWN AS 9.2 KW ON ELEC AND 8KW | | ON MECH? PLEASE CORRELATE. | | | | PLEASE SEE THAT MOST NOTES WERE ADDRESS- | | ED FROM FIRST REVIEW. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|