2003-06-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A.2 BATHROOM SHALL COMPLY SECTION
 11-4.23 AND ALL SUBSECTIONS. PROVIDE
 DETAILS. 4TH FLOOR BUSINESS TENANT.
 2) SHT A.2 FOURTH FLOOR BUSINESS TENANT,
 PER TABLE 403.1 A DRINKING FOUNTAIN IS
 REQUIRED. ALSO SEE SECTION 410.1
 3) SHT A.2 5TH FLOOR SOUTH RESIDENTIAL,
 PER TABLE 403.1 A WASH MACHINE CONNECT-
 ION IS REQUIRED.
 4) SHT A.2 ROOF PLAN, SUBMIT CALCULAT-
 IONS FOR PRIMARY AND SECONDARY ROOF
 DRAINS. SHOW 1/2 AREA FOR ALL VERTICAL
 WALLS INCLUDING PARAPETS. SHOW SLOP OF
 ROOF TO DRAINS. SECTIONS 1106 & 1107 AND
 ALL SUBSECTIONS.
 5) SHT P-1 KEY NOTES: #11, THE RELIEF
 VALVE SHALL DISCHARGE FULL SIZE. SECTION
 504.7.1. - #9 MINIMUM EMERGENCY PAN
 DRAIN SIZE IS 3/4". SECTION 504.8.1
 SHT P-1 WATER RISER DIAGRAM, AIR CHAMB-
 ERS ARE NOT APPROVED. WATER HAMMER AR-
 RESTORS REQUIRED BY 604.9 SHALL BE LOCA-
 TED AT WASH MACHINES, ICE MAKERS, AND
 DISHWASHERS.
 6) ALL ABANDONED/DEMO'ED PIPING SHALL BE
 INSPECTED PRIOR TO COVERING.
 7) SHT P-1 GENERAL NOTES: #16, AIR
 CHAMBERS ARE NOT APPROVED. DELETE REFER-
 ENCE.
 8) SHT P-1 SUBMIT RISERS FOR THE RELIEF
 VALVE DISCHARGE LINE AND THE EMERGENCY
 PAN DRAIN LINE. SHOW PIPE SIZE, TYPE OF
 MATERIAL, AND TERMINATION POINT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692