2003-06-27 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 11 |
| |
| 1) SHT A.2 BATHROOM SHALL COMPLY SECTION |
| 11-4.23 AND ALL SUBSECTIONS. PROVIDE |
| DETAILS. 4TH FLOOR BUSINESS TENANT. |
| 2) SHT A.2 FOURTH FLOOR BUSINESS TENANT, |
| PER TABLE 403.1 A DRINKING FOUNTAIN IS |
| REQUIRED. ALSO SEE SECTION 410.1 |
| 3) SHT A.2 5TH FLOOR SOUTH RESIDENTIAL, |
| PER TABLE 403.1 A WASH MACHINE CONNECT- |
| ION IS REQUIRED. |
| 4) SHT A.2 ROOF PLAN, SUBMIT CALCULAT- |
| IONS FOR PRIMARY AND SECONDARY ROOF |
| DRAINS. SHOW 1/2 AREA FOR ALL VERTICAL |
| WALLS INCLUDING PARAPETS. SHOW SLOP OF |
| ROOF TO DRAINS. SECTIONS 1106 & 1107 AND |
| ALL SUBSECTIONS. |
| 5) SHT P-1 KEY NOTES: #11, THE RELIEF |
| VALVE SHALL DISCHARGE FULL SIZE. SECTION |
| 504.7.1. - #9 MINIMUM EMERGENCY PAN |
| DRAIN SIZE IS 3/4". SECTION 504.8.1 |
| SHT P-1 WATER RISER DIAGRAM, AIR CHAMB- |
| ERS ARE NOT APPROVED. WATER HAMMER AR- |
| RESTORS REQUIRED BY 604.9 SHALL BE LOCA- |
| TED AT WASH MACHINES, ICE MAKERS, AND |
| DISHWASHERS. |
| 6) ALL ABANDONED/DEMO'ED PIPING SHALL BE |
| INSPECTED PRIOR TO COVERING. |
| 7) SHT P-1 GENERAL NOTES: #16, AIR |
| CHAMBERS ARE NOT APPROVED. DELETE REFER- |
| ENCE. |
| 8) SHT P-1 SUBMIT RISERS FOR THE RELIEF |
| VALVE DISCHARGE LINE AND THE EMERGENCY |
| PAN DRAIN LINE. SHOW PIPE SIZE, TYPE OF |
| MATERIAL, AND TERMINATION POINT. |
| |