Plan Review Notes
Plan Review Notes For Permit 03060496
Permit Number 03060496
Review Stop E
Sequence Number 1
Notes
Date Text
2003-06-25 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE, SD`S ARE REQ'D TO
 BE 5' FROM RETURN AIR. IT IS NOTED
 3' FROM ALL OTHERS WHICH IS CORRECT.
 NFPA-72 8-1.4
  
 2)NOTE: MISSING TWO SMALL APPLIANCE
 CIRCUITS FOR EACH UNIT.
 A MIN OF TWO REQ`D PER 210-52/ 210-11C-1
  
 3)NOTE: PLEASE CLARIFY MISSING MIN REQ`D
 WASHER IN SOUTH UNIT? 210-11C-2
 210-52
  
 4)NOTE: PLEASE SEE 424-3 FOR 125% MIN
 OCP FOR AHU'S.
  
 5)NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR EXISTING SERVICE AND
 SHOW ANY NEW LOADS ADDED.
 PLEASE ALSO SEE PLANS, SHOWS ELECTRICAL
 ROOM ON GROUND FLOOR? PLEASE VERIFY
 IF ROOM HAS MOVED FROM MEZZ LEVEL,2ND
 FLR?
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 NEW DISC`S. 110-9/215-5
  
 7)NOTE: PLEASE REDO LOAD CALCULATIONS
 FOR MIN LOADS REQ`D UNDER 220.
 PLEASE ALSO SEE MIN LOADS FOR RANGE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 PLEASE ALSO NOTE VALUE OF WORK TO BE
 UPGRADED DUE TO WORK BEING DONE.
 VALUE SHOWN AT 10,000 NOW IS WAY UNDER-
 -VALUED. 104.6.5