Plan Review Notes
Plan Review Notes For Permit 03060496
Permit Number 03060496
Review Stop B
Sequence Number 1
Notes
Date Text
2003-06-30 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03060496
 ADD: 215 S OLIVE AVE
 CONT: RAYMOND NORDINE
 TEL: (561)252-1662
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) F 103.1 EXISTING BUILDINGS WITHIN THE
 FIRE DISTRICT.
 AN EXISTING BUILDING SHALL NOT BE HERE-
 AFTER BE INCREASED IN HEIGHT OR AREA
 UNLESS IT IS OF THE TYPE OF CONSTRUCTION
 PERMITTED FOR NEW BUILDINGS WITHIN THE
 FIRE DISTRICT OR IS ALTERED TO COMPLY
 WITH THE REQUIREMENTS FOR SUCH TYPE OF
 CONSTRUCTION. NOR SHALL ANY BUILDING BE
 HEREAFTER EXTENDED ON ANY SIDE, NOR
 SQUARE FOOTAGE OR FLOORS ADDED WITHIN
 THE EXISTING BUILDING UNLESS SUCH MODIF-
 ICATIONS ARE OF A TYPE OF CONSTRUCTION
 PERMITTED FOR NEW BUILDINGS WITHIN THE
 FIRE DISTRICT.A-2 NOTE 18.
  
 2) 1012.1.4 DURING ITS SWING, ANY DOOR
 IN A MEANS OF EGRESS SHALL LEAVE UNOBSTR
 UCTED AT LEAST ONE HALF OF THE REQUIRED
 WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY,
 OR LANDING, NOR PROJECT MORE THAN 7" IN-
 TO THE REQUIRED WIDTH OF AN AISLE, CORRI
 DOR, PASSAGEWAY OR LANDING, WHEN FULLY
 OPEN, SEE ENTRY DOOR (A).FIFTH FLOOR
 LANDING OF MAIN STAIR.
  
 3)SHEET A-4 STAIR PLAN TO ROOF DETAIL(2)
 INDICATES A 8" RISE, 1007.3.` MAXIMUM OF
 7"RISE, TREADS A MINIMUM OF 11".
  
 4)1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 5) SOUTH TENANT INDICATES A WORK/ LOFT
 WITH THE FOURTH FLOOR BEING BUSINESS,
 THE BATHROOM IS ELEVATED FROM THE MAIN
 FLOOR BY THREE RISERS, PROVIDE INFORMA-
 TION FOR VERTICAL ACCESSIBILITY.11-4.1.6
  
 6) THIS SAME BATHROOM REQUIRES A FLOOR
 THE SAME LEVELAAS THE BATH, 1007.2.4.,
 IF THIS IS CONSIDERED BUSINESS. NO EXCEP
 TION AS IN R-3.
  
 7) SPIRAL STAIRWAY: PROVIDE MANUFACTURER
 INFORMATION, THAT THE SPIRAL STAIR COM-
 PLIES WITH ALL SECTIONS OF 1007.8.2.3 &
 1007.8.3. STAIRWAY & HANDRAIL & GUARD-
 RAIL SYSTEMS.
  
 8) SHEET S-1 LIVE LOADS, ARE TO BE TAKEN
 FOR THE OCCUPANCY THE FOURTH FLOOR IS
 CONSIDERED THE WORK FLOOR OF THE WORK/
 LIVE LOFT THE FLOOR LIVE LOAD MINIMUM
 FOR OFFICE IS 50 PSF WITHOUT FILE
 CABINETS ? THE FIFTH FLOOR FOR LIVING
 AREAS SHOULD BE 40 PSF ONLY SLEEPING
 ROOMS IS 30 PSF. NO MENTION AS TO THE
 LOADING FOR THE ATTIC STORAGE PSF?
  
 9)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 MISSING THE DESIGN WIND PRESSURES FOR
 THE NEW ROOF SYSTEM,SEE FIGURE 1606.2(C)
 FOR INTERIOR ZONES, EDGE AND ZONE 3.
 PROVIDE THE MEAN ROOF HEIGTH?
 ALSO GIVE PRESSURES FOR THE NEW EXTERIOR
 DOOR AND SKYLIGHTS?
  
 10)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS FOR
 A) EXTERIOR DOOR
 B) SKYLIGHTS
 C) ROOFING ASSEMBLIES (FIRE DISTRICT)
 PROVIDE MAN SPEC FOR ROOF AND INSU
 LATION FOR FIRE TYPE A OR B AND
 ATTACHMENT.
  
 11)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 12)1006.1.3.1 PENETRATIONS INTO AND
 THROUGH A STAIRWAY ENCLOSURE ASSEMBLY
 ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, DUCTWORK AND EQUIPMENT NECESSARY
 FOR THE INDEPENDENT STAIR PRESSURIZATION
 SPRINKLER PIPING, STANDPIPES AND ELECTRI
 CALCONDUIT SERVING THE STAIRWAY AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQ IN. SUCH PENETRATIONS SHALL BE PRO
 TECTED IN ACCORDANCE WITH 705.4
  
 13)1503.4 ROOF DRAINS UNLESS ROOFS ARE
 SLOPED TO DRAIN OVER THE ROOF EDGE, ROOF
 DRAINS SHALL BE INSTALLED AT THE LOWEST
 POINT OF THE ROOF. WHERE REQUIRED FOR
 ROOF DRAINAGE,SCUPPERS SHALL BE LOCATED
 AS DETERMINED BY THE ROOF SLOPE AND CON-
 TRIBUTING ROOF AREA.
  
 14)1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 ABOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.
  
 15)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGTH IN ACCORDANCE WITH TABLE 1511.7.
  
 16)3003.6.2 VENTS SHALL BE LOCATED
 BELOW THE FLOOR OR FLOORS AT THE TOP OF
 THE HOISTWAY, AND SHALL BE EITHER DIR-
 ECTLY TO THE OUTER AIR OR THROUGH NON-
 COMBUSTIBLE DUCTS TO THE OUTER AIR.
  
 17)3003.6.3 THE AREA OF THE VENTS
 SHALL BE NOT LESS THAN 3 SQ FT FOR EACH
 ELEVATOR CAR, WHICHEVER IS GREATER.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW