Plan Review Notes For Permit 03060493 |
Permit Number |
03060493 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-06-11 00:00:00 | UNSAT | | ~~~~~ | | `~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | THE SCOPE OF THIS WORK REQUIRES AN | | ELECTRICAL PERMIT AND NONE WAS APPLIED | | FOR. | | PLEASE HAVE ELECTRICAL CONTRACTOR SUBMIT | | THE FOLLOWING WITH THE APPLICATION. | | | | 1} SIZE OF THE EXISTING SERVICE WITH | | LOAD CALCULATIONS INCLUDING ALL NEW | | ADDED LOADS. | | | | 2} PLEASE LIST THE REQ'D BATH(S) | | CIRCUIT(S). PER 210-11-C-3 | | MUST BE 20A AND #12AWG. | | | | 3} PLEASE LIST THE REQ'D ARC | | FAULT PROTECTED CIRCUITS ON PANEL | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | CIRCUIT PROTECTION. PER 210-12 | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|