2003-06-25 00:00:00 | ******CORRECTIONS******* |
| |
| SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)BEDROOMS ARE REQUIRED TO HAVE |
| EMERGENCY EGRESS FBC1005.4.A 38" HIGH |
| SINGLE HUNG WINDOW DOES NOT COMPLY. |
| |
| 2.)THE WINDOW AT THE TUB LOCATION |
| MUST COMPLY WITH FBC2405.2. |
| |
| 3.)ADDITIONS OVER 25% MUST COMPLY |
| WITH FBC 3401.7.1.2.1. |
| |
| 4.)SUBMIT TWO COPIES OF PRODUCT |
| APPROVALS FOR MULLIONS AND SHINGLES. |
| THE SHINGLE PRODUCT APPROVAL MAY BE |
| SUBMITTED WITH THE ROOF PERMIT |
| APPLICATION. |
| |
| 5.)SEPARATE PERMITS REQUIRED. |
| |
| 6.)ENERGY CALCS REQUIRED FBC13-101.2. |
| |
| 7.)HOW IS THE BASE PLATE ATTACHED |
| TO THE CONCRETE?GIVE ATTACHMENT SIZE |
| AND TYPE, EMBEDMENT, DISTANCE. |
| |
| 8.)PROVIDE A ROOF SHEATHING ATTACHMENT |
| SCHEDULE. |
| |
| 9.)IT IS UNCLEAR WHICH HETA ATTACHMENT |
| IS SPECIFIED ON THE WALL SECTION. REVISE |
| AND GIVE DESIGN UPLIFT FOR ALL |
| ATTACHMENTS WITH STRUCTURAL CALCULATIONS |
| OR SEALED BY AN ENGINEER, FBC104.3.1.1. |
| |
| 10.)FIRESTOP REQUIRED FBC 705.3. |
| |
| 11.)ATTIC ACCESS REQUIRED FBC2309.6. |
| |
| 12.)ADDITIONAL FEES REQUIRED, $4.48. |
| |
| 13.)PROVIDE A ROOF FRAMING PLAN. |
| |
| 14.)DESIGN INFORMATION IS REQUIRED |
| TO BE ON THE PLAN, FBC 1606.1.7. |
| |
| 15.)THE SECOND SHEET HAS A BLANK |
| TITLE BLOCK. |
| |
| 16.)ALL CHANGES MUST BE APPROVED BY |
| HISTORIC BEFORE RESUBMITTAL. |
| |
| CLOUD ALL CHANGES BEFORE RESUBMITTAL. |
| PROVIDE A WRITTEN RESPONSE TO ALL ITEMS |
| EXPLAINING HOW IT HAS BEEN ADDRESSED. |