2003-06-19 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE CORRELATE ELECTRICAL
 DIAGRMA WITH EQUIPMENT BEING INSTALLED.
 HEAT PUMP NOT SHOWN ON RISER?
 WIRE/CONDUIT ETC.
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 WITH EXISTING AND NEW LOADS.
 PLEASE SHOW SIZE OF EXISTING SERVICE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  