2003-06-24 00:00:00DENIED:MECHANICAL PERMIT 03060465
  
 ENERGY CALCULATIONS INDICATE 2721 SQ FT
 OF CONDITIONED FLOOR SPACE THE COOLING
 SYSTEM INDICATES ONLY A 3 1/2 TON SYSTEM
 WHEREAS THE EQUIPMENT SCHEDULE ON THE
 PLAN INDICATES A 5 TON SYSTEM.A 3 1/2
 TON SYSTEM FOR THIS SQ FOOTAGE SEEMS
 INADEQUATE.PLEASE CLARIFY.
  