2003-06-24 00:00:00 | DENIED:MECHANICAL PERMIT 03060465 | | | | ENERGY CALCULATIONS INDICATE 2721 SQ FT | | OF CONDITIONED FLOOR SPACE THE COOLING | | SYSTEM INDICATES ONLY A 3 1/2 TON SYSTEM | | WHEREAS THE EQUIPMENT SCHEDULE ON THE | | PLAN INDICATES A 5 TON SYSTEM.A 3 1/2 | | TON SYSTEM FOR THIS SQ FOOTAGE SEEMS | | INADEQUATE.PLEASE CLARIFY. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|