Notes |
Date |
Text |
2003-07-12 00:00:00 | *******CORRECTIONS****** | | | | 1.)FAC 61G15-23.002(2), A TITLE BLOCK | | (ENGINEER) ON EACH PAGE IS REQUIRED. | | | | 2.)HAVE THE ENGINEER INITIAL ALL | | CHANGES MADE IN INK TO THE PLAN. | | | | 3.)NO ATTACHMENTS WERE GIVEN FOR THE | | RAILING.SEE THE PREVIOUS CORRECTION | | LIST; GUARDRAIL TO COMPLY WITH FBC | | 1608.2.2.HAVE THE ENGINEER REVIEW AND | | SEAL THE GUARDRAIL DETAIL AND | | ATTACHMENTS, AND INDICATE ON THE PLAN | | THAT IT COMPLIES WITH FBC1608.2.2. | | | | 4.)THE DOOR PRODUCT APPROVAL SUBMITTED | | HAS A PRODUCT LIMITATION OF +50/-46 PSF. | | THE FRENCH DOOR ACCORDING TO YOUR PLAN | | MUST HAVE A MINIMUM OF +49/-57 PSF | | RATING.ANY NEW PRODUCT APPROVALS | | SUBMITTED MUST BE APPROVED BY THE | | HISTORIC PRESERVATION DIVISION. | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | [email protected] |
|