Plan Review Notes
Plan Review Notes For Permit 03060179
Permit Number 03060179
Review Stop B
Sequence Number 1
Notes
Date Text
2003-06-06 00:00:00BUILDING DENIED
  
 1) SUBMIT RECEIPT FOR IMPACT FEES.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT SOIL BORING TEST REPORT.
  
 4) REVISE/CLARIFY NOTE #1 ON SHEET A4.
 HANDRAIL AND GUARDRAIL ARE NOT THE SAME.
 SEE FBC 1007.5.1 FOR HANDRAIL HEIGHT.
  
 5) THE "USP" TP6X AND TP8X CONNECTORS
 SPECIFIED FOR THE STUD PLATE CONNECTION
 ON THE WD. FRAME TO CONC. WALL DETAIL ON
 A6 ARE NOT LISTED IN THE 2003 USP
 CATALOG. ARE THESE "USP" SPT OR SPTH
 CONNECTORS?
  
 6) SPECIFY THE CONNECTOR FOR THE FLOOR
 TRUSS TO THE CONC. WALL ON DETAIL 1/S2.
  
 7) SPECIFY THE CONNECTORS FOR EACH END
 OF THE FLOOR GIRDER TRUSS SHOWN ON
 LOWER ROOF PLAN AT THE CENTER OF THE
 STRUCTURE AND SUPPORTED IN THE CENTER BY
 THE STEEL COLUMN.
  
 8) REVISE THE UPLIFT CAPACITIES OF THE
 TRUSS CONNECTORS ON SHEETS S2 AND S3 TO
 VALUES THAT DO NOT INCLUDE A ONE-THIRD
 INCREASE ON THE STEEL CALCULATIONS. SEE
 FBC 1609.4.3 AND 2003 USP CATALOG.
  
 9) THE OWNER AND CONTRACTOR INFORMATION
 ON THE ENERGY CALCULATIONS AND
 APPLICATION DO NOT MATCH THE CITY AND
 COUNTY RECORDS. PLEASE CORRECT.
  
 10) THE ENERGY CALC. FORM IS REQUIRED TO
 BE SIGNED BY THE OWNER/AGENT.
  
 11) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ARCHED TOP FIXED GLASS WINDOWS
 - STRUCTURAL MULLIONS (EXPIRED 5/1/03)
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714