2003-07-25 00:00:00 | DENIED | | REFERENCE: FBC-2001 FUEL GAS | | | | 1) TABLES SUBMITTED WITH PLANS ARE NOT | | APPROVED. | | 2) PLEASE INDICATE MANUFACTURE OF PE | | PIPE AND SUBMIT MANUF SHEETS. MANUF. | | INFORMATION REQUIRED FOR SIZING, CHART | | FROM MANUFACTURE REQUIRED. | | 3) DISTANCE FROM METER AND SIZE OF PIPE | | SHOW THAT A 1/2 POUND SYSTEM WILL BE | | INSUFFICIENT. EITHER 2" PIPE WILL BE RE- | | QUIRED OR INCREASE DELIVERY PRESSURE TO | | A 2 LB SYSTEM WITH REGULATORS. | | 4) CUT SHEET WILL BE REQUIRED FOR REG- | | ULATORS IF 2 LB SYSTEM IS USED. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|