Plan Review Notes
Plan Review Notes For Permit 03060103
Permit Number 03060103
Review Stop E
Sequence Number 1
Notes
Date Text
2003-06-10 00:00:00~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 NOTE THAT AN ELECTRICAL PERMIT IS
 NEEDED FOR THIS WORK,NO ELECTRICAL
 CONTRACTOR IS SIGNED ON THE APPLICATION
 AND THEREFORE MUST APPLY SEPARATELY.
  
 PLEASE PROVIDE THE FOLLOWING WITH
 ELECTRICAL APPLICATION:
  
 1} LOAD CALCULATIONS FOR THE SERVICE AND
 THE SIZE OF THE EXISTING SERVICE.
  
 2} A RISER DIAGRAM IF A NEW SERVICE IS
 BEING INSTALLED.
  
 3} A DRAWING INDICATING THE LOCATION OF
 THE NEW EQUIPMENT AND THE SIZE OF THE
 WIRE ,CONDUIT AND OCP SUPPLYING THE NEW
 EQUIPMENT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  