Plan Review Notes
Plan Review Notes For Permit 03060087
Permit Number 03060087
Review Stop B
Sequence Number 2
Notes
Date Text
2003-11-20 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)THE NOTICE OF COMMENCEMENT
 SUBMITTED WAS FOR 1017 SELKIRK (WRONG
 ADDRESS).
  
 3.)SEE PREVIOUS LIST, ITEM #4.THE
 INSULATION CANNOT BE R4.0 WHEN THE
 ENERGY CALC SPECIFIES A MINIMUM OF R4.2.
  
 4.)SEE PREVIOUS LIST, ITEM #9, SHEET
 2 STILL REFERS TO "UNLOAD DESIGN".
  
 5.)SEE PREVIOUS LIST, ITEM #12,
 CONNECTOR SCHEDULE HAS AN UPLIFT FOR
 TWO STRAPS THAT IS LESS THAN THE UPLIFT
 ON THE PLAN FOR THAT CONNECTOR.REVISE
 THE CONNECTOR SCHEDULE UPLIFT.
  
 6.)SEE PREVIOUS LIST, ITEM #13,
 PROVIDE A WINDOW & DOOR BUCK ATTACHMENT
 DETAIL.
  
 7.)SEE PREVIOUS LIST, ITEM #16,
 PROVIDE TWO COPIES OF THE WINDOW
 MULLION PRODUCT APPROVAL.
  
 8.)ADDITIONAL FEES DUE, $364.43
 (RADON AND VALUE ADJUSTMENT), SEE
 ATTACHED BZ233275.
  
 9.)SEE PREVIOUS LIST.WHEN
 RESUBMITTING, ALL CHANGES MUST BE
 CLEARLY MARKED WITH CLOUDS OR TRIANGLES.
  
 10.) THE CHANGES TO A SEALED PLAN MUST
 BE INITIALED BY THE ENGINEER.
  
 11.)THE ENGINEER'S LICENSE NUMBER
 IS REQUIRED TO BE ON EACH SHEET, FAC
 61G15-23.002.
  
 12.)SEE ATTACHED NOTICE REGARDING
 FS553.80(2)(B).
  
 13.)PROVIDE A KEY PLAN AND HURRICANE
 SHUTTER INSTALLATION SCHEDULE (SEE
 ATTACHED).
  
 14.)IDENTIFY THE JOB ON THE TITLE
 BLOCK (ADDRESS OR LOT NUMBER).
  
 15.)THERE IS AN "EXTENDED WALL".
 PROVIDE A DETAIL.A WALL IS NOT
 "DECORATION PURPOSE ONLY", A WALL IS
 ALWAYS A STRUCTURAL ELEMENT.SHOW ON
 THE FOUNDATION PLAN.