2003-11-20 00:00:00 | *****CORRECTIONS****** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 |
| |
| 1.)SEPARATE PERMITS REQUIRED. |
| |
| 2.)THE NOTICE OF COMMENCEMENT |
| SUBMITTED WAS FOR 1017 SELKIRK (WRONG |
| ADDRESS). |
| |
| 3.)SEE PREVIOUS LIST, ITEM #4.THE |
| INSULATION CANNOT BE R4.0 WHEN THE |
| ENERGY CALC SPECIFIES A MINIMUM OF R4.2. |
| |
| 4.)SEE PREVIOUS LIST, ITEM #9, SHEET |
| 2 STILL REFERS TO "UNLOAD DESIGN". |
| |
| 5.)SEE PREVIOUS LIST, ITEM #12, |
| CONNECTOR SCHEDULE HAS AN UPLIFT FOR |
| TWO STRAPS THAT IS LESS THAN THE UPLIFT |
| ON THE PLAN FOR THAT CONNECTOR.REVISE |
| THE CONNECTOR SCHEDULE UPLIFT. |
| |
| 6.)SEE PREVIOUS LIST, ITEM #13, |
| PROVIDE A WINDOW & DOOR BUCK ATTACHMENT |
| DETAIL. |
| |
| 7.)SEE PREVIOUS LIST, ITEM #16, |
| PROVIDE TWO COPIES OF THE WINDOW |
| MULLION PRODUCT APPROVAL. |
| |
| 8.)ADDITIONAL FEES DUE, $364.43 |
| (RADON AND VALUE ADJUSTMENT), SEE |
| ATTACHED BZ233275. |
| |
| 9.)SEE PREVIOUS LIST.WHEN |
| RESUBMITTING, ALL CHANGES MUST BE |
| CLEARLY MARKED WITH CLOUDS OR TRIANGLES. |
| |
| 10.) THE CHANGES TO A SEALED PLAN MUST |
| BE INITIALED BY THE ENGINEER. |
| |
| 11.)THE ENGINEER'S LICENSE NUMBER |
| IS REQUIRED TO BE ON EACH SHEET, FAC |
| 61G15-23.002. |
| |
| 12.)SEE ATTACHED NOTICE REGARDING |
| FS553.80(2)(B). |
| |
| 13.)PROVIDE A KEY PLAN AND HURRICANE |
| SHUTTER INSTALLATION SCHEDULE (SEE |
| ATTACHED). |
| |
| 14.)IDENTIFY THE JOB ON THE TITLE |
| BLOCK (ADDRESS OR LOT NUMBER). |
| |
| 15.)THERE IS AN "EXTENDED WALL". |
| PROVIDE A DETAIL.A WALL IS NOT |
| "DECORATION PURPOSE ONLY", A WALL IS |
| ALWAYS A STRUCTURAL ELEMENT.SHOW ON |
| THE FOUNDATION PLAN. |