Plan Review Notes
Plan Review Notes For Permit 03060043
Permit Number 03060043
Review Stop P
Sequence Number 1
Notes
Date Text
2003-06-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) INDICATE OCCUPANCY OF UNIT. MORE
 COMMENTS MAY ARISE DEPENDING ON RESPONSE
 2) PROVIDE A SANITARY AND A WATER RISER
 DIAGRAM. SECTION 104.2.1 CHAPTER 1
 3) A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1. ALSO SEE SECTION 410.1.
 4) WATER CLOSET SHALL BE 18" OFF WALL TO
 CENTER OF FIXTURE. FIG. 28. FIGURES 30A
 AND 30E ARE FOR STALLS ONLY NOT TOILET
 ROOMS.
 5) 11-4.22.2 DOOR SHALL NOT OPEN INTO
 THE CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE.
  
 REVIEW BY KEN STEVENS