2003-07-19 00:00:00PROVISO:
 NOTES DATED 6/26/03 BY HAROLD MOSER
 1.HYDRONIC PIPING SYSTEMS SHALL BE
 TESTED HYDRONICALLY AT ONE-HALF TIMES
 THE MAXIMUM SYSTEM DESIGN PRESSURE, BUT
 NOT LESS THAN 100 PSI.FROM RISER TO
 A/C #1 & 2.
 2.HAVE PIPE DIAGRAM WITH PLANS WITH
 PLANS.
 3.HAVE EQUIPMENT SPECIFICATION WITH
 PLANS.
  
 NOTES FROM PATTY KRAUSS 7-19-03
 1.PLAN SHEET M-1 INDICATES "PACKAGE
 UNITS".PLEASE CLARIFY, ARE UNITS A
 PART OF THE BUILDING A/C A CONDENSER
 WATER SYSTEM?ARE THESE UNITS ACTUALLY
 HEAT PUMPS?
 2.SHOULD UNITS BE HEAT PUMPS, INDICATE
 LOCATION, DUCT SIZE AND MATERIAL OF
 OUTSIDE AIR.
 3.PLEASE NOTE DUCT SMOKE DETECTORS TO
 HAVE NOTIFICATION AS PER NFPA 90A -
 4-4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.