Plan Review Notes For Permit 03060041 |
Permit Number |
03060041 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-07-19 00:00:00 | PROVISO: | | NOTES DATED 6/26/03 BY HAROLD MOSER | | 1.HYDRONIC PIPING SYSTEMS SHALL BE | | TESTED HYDRONICALLY AT ONE-HALF TIMES | | THE MAXIMUM SYSTEM DESIGN PRESSURE, BUT | | NOT LESS THAN 100 PSI.FROM RISER TO | | A/C #1 & 2. | | 2.HAVE PIPE DIAGRAM WITH PLANS WITH | | PLANS. | | 3.HAVE EQUIPMENT SPECIFICATION WITH | | PLANS. | | | | NOTES FROM PATTY KRAUSS 7-19-03 | | 1.PLAN SHEET M-1 INDICATES "PACKAGE | | UNITS".PLEASE CLARIFY, ARE UNITS A | | PART OF THE BUILDING A/C A CONDENSER | | WATER SYSTEM?ARE THESE UNITS ACTUALLY | | HEAT PUMPS? | | 2.SHOULD UNITS BE HEAT PUMPS, INDICATE | | LOCATION, DUCT SIZE AND MATERIAL OF | | OUTSIDE AIR. | | 3.PLEASE NOTE DUCT SMOKE DETECTORS TO | | HAVE NOTIFICATION AS PER NFPA 90A - | | 4-4.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|