Plan Review Notes For Permit 03060041 |
Permit Number |
03060041 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-06-21 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) INDICATE OCCUPANCY OF UNIT. MORE | | COMMENTS MAY ARISE DEPENDING ON RESPONSE | | 2) PROVIDE A SANITARY AND A WATER RISER | | DIAGRAM. | | 3) DRINKING FOUNTAIN IS REQUIRED PER | | TABLE 403.1. ALSO SEE SECION 410.1 | | 4) SUBMIT DETAIL FOR TOILET ROOM PER | | SECTION 11-4.22 AND ALL SUBSECTION. | | WATER CLOSET SHALL BE 18" TO WALL FROM | | CENTER OF FIXTURE PER FIG 28. FIGURES | | 30A AND 30E ARE FOR TOILET STALLS NOT | | TOILET ROOMS. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 |
|